Adverse impact of STATCOM on the performance of distance relay

FACTS devices like the Static Synchronous Compensator (STATCOM), are mostly used to enhance the maximum power transfer capability of the transmission Line (TL) system. AMatlab simulation model of Distance Relay protection ofTL, with connected STATCOM at the mid-point for optimum power transfer is pr...

Full description

Saved in:
Bibliographic Details
Main Authors: Aker, Elhadi Emhemad, Othman, Mohammad Lutfi, Aris, Ishak, Abdul Wahab, Noor Izzri, Hizam, Hashim, Emmanuel, Osaji
Format: Article
Language:English
Published: Institute of Advanced Engineering and Science 2017
Online Access:http://psasir.upm.edu.my/id/eprint/60785/1/Adverse%20impact%20of%20STATCOM%20on%20the%20performance%20of%20distance%20relay.pdf
http://psasir.upm.edu.my/id/eprint/60785/
https://www.researchgate.net/profile/Mohammad_Lutfi_Othman/publication/317659857_Adverse_impact_of_STATCOM_on_the_performance_of_distance_relay/links/59477b5eaca2722db4a617c8/Adverse-impact-of-STATCOM-on-the-performance-of-distance-relay.pdf
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Universiti Putra Malaysia
Language: English
Description
Summary:FACTS devices like the Static Synchronous Compensator (STATCOM), are mostly used to enhance the maximum power transfer capability of the transmission Line (TL) system. AMatlab simulation model of Distance Relay protection ofTL, with connected STATCOM at the mid-point for optimum power transfer is presented. The STATCOM’s impact on the operation of the relay is assessed with the effects on the relay misoperation in the third zone of protection coverage, during fault conditions, in four different locations.The wrong measured fault impedance by relay resulted to misoperation in zone 3 (under reach phenomena). The simulation result indicates a slight increase in the measured impedance of 1.33 Ω over the actually expected impedance setting (72.02 Ω) of the relay at 220 km protection coverage of zone 3 along the TL. This variation is about 4 km distance outside the expected distance protection coverage for fault in zone 3 as proven.