Modeling and validation of an active chilled beam terminal unit

In this paper, a simplified hybrid model is proposed for an active chilled beam (ACB) terminal unit. Based on the conservation equations of mass and energy, the model demonstrates the air entrainment characteristics in the air chamber and the heat transfer process in cooling coil. Compared with the...

全面介紹

Saved in:
書目詳細資料
Main Authors: Ji, Ke, Cai, Wenjian, Zhang, Xin, Wu, Bingjie, Ou, Xianhua
其他作者: School of Electrical and Electronic Engineering
格式: Article
語言:English
出版: 2021
主題:
在線閱讀:https://hdl.handle.net/10356/151587
標簽: 添加標簽
沒有標簽, 成為第一個標記此記錄!
機構: Nanyang Technological University
語言: English