Insulation level and clearances for 230 kV air insulated substation
This paper analyzes the insulation level and air clearances of 230 kV air insulated substation. In order to get the BIL, the crest voltage at any equipment are required. By applying simplified calculation method taken from IEEE Std. 1313.2-1999 and IEEE Std. 1427-2006 compared with digital simulatio...
Saved in:
主要作者: | |
---|---|
格式: | Conference or Workshop Item |
出版: |
2015
|
在線閱讀: | http://www.scopus.com/inward/record.url?partnerID=HzOxMe3b&scp=84905405566&origin=inward http://cmuir.cmu.ac.th/handle/6653943832/39049 |
標簽: |
添加標簽
沒有標簽, 成為第一個標記此記錄!
|
機構: | Chiang Mai University |
總結: | This paper analyzes the insulation level and air clearances of 230 kV air insulated substation. In order to get the BIL, the crest voltage at any equipment are required. By applying simplified calculation method taken from IEEE Std. 1313.2-1999 and IEEE Std. 1427-2006 compared with digital simulation. The simulations have been implemented using simplified models via EMTP-ATP. The BIL required and BIL selected from simplified calculation may give the insulation level not in the range, so the digital simulation would be the better choice. The effect of elevation from sea level as well as the switching surge have been considered for insulation levels and clearances. © 2014 IEEE. |
---|