Ground potential rise from lightning overvoltage in communication station

This paper compares the ground potential rise (GPR) from lightning overvoltage with two different grounding methods, no bonding and bonding of grounding systems, between the communication tower and main ground bar (MGB) of the TOT communication station. Direct lightning stroke to the communication t...

全面介紹

Saved in:
書目詳細資料
主要作者: T. Thanasaksiri
格式: Conference Proceeding
出版: 2018
主題:
在線閱讀:https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=52949141876&origin=inward
http://cmuir.cmu.ac.th/jspui/handle/6653943832/60289
標簽: 添加標簽
沒有標簽, 成為第一個標記此記錄!
機構: Chiang Mai University
實物特徵
總結:This paper compares the ground potential rise (GPR) from lightning overvoltage with two different grounding methods, no bonding and bonding of grounding systems, between the communication tower and main ground bar (MGB) of the TOT communication station. Direct lightning stroke to the communication tower gives the higher overvoltage than the lightning stroke on distribution overhead line and also higher than the induced voltage surge. The ground bonding gives the less lightning overvoltage when compared with no ground bonding so the ground bonding in communication station is recommended. To reduce the damage from lightning overvoltage occur to the protecting equipments especially for data transmission interface (DTI), the protectors should have a higher energy discharge capability. © 2008 IEEE.