IDENTIFICATION OF A HOTEL BUILDING ENERGY CONSERVATION OPPORTUNITIES IN BANDUNG
Hotel is one of an example of commercial buildings with high energy consumption which caused by the customer’s demand of good service and comfort while using the facility. Hence, this study is conducted to identify Energy Conservation Opportunity (ECO) in a 4-star hotel building in Bandung to imp...
Saved in:
Main Author: | |
---|---|
Format: | Final Project |
Language: | Indonesia |
Subjects: | |
Online Access: | https://digilib.itb.ac.id/gdl/view/44910 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Institut Teknologi Bandung |
Language: | Indonesia |
id |
id-itb.:44910 |
---|---|
spelling |
id-itb.:449102019-11-13T09:53:43ZIDENTIFICATION OF A HOTEL BUILDING ENERGY CONSERVATION OPPORTUNITIES IN BANDUNG Dwisstya Utami, Amanda Teknik (Rekayasa, enjinering dan kegiatan berkaitan) Indonesia Final Project Hotel building, energy conservation, IKE, SC, EnergyPlus INSTITUT TEKNOLOGI BANDUNG https://digilib.itb.ac.id/gdl/view/44910 Hotel is one of an example of commercial buildings with high energy consumption which caused by the customer’s demand of good service and comfort while using the facility. Hence, this study is conducted to identify Energy Conservation Opportunity (ECO) in a 4-star hotel building in Bandung to improve the building energy performance. Evaluating EUI (Energy Use Intensity) is done to achieve the objective. The lower EUI values, shows the better energy building performance. Evaluation of EUI value is done by simulation using Energyplus V8.4 software. The result shows that the building actual condition has EUI value of 252,20 kWh/m2/year with the condition of temperature setpoint often not met. The desired temperature setpoint is 19ºC while the room temperature shows higher temperature. There are several parameters changed such as SC glass, temperature setpoint, and doubled chiller capacity. The result shows that the most effective energy saving method attained when chiller capacity increased and temperature setpoint set higher. When the entire hotel area are set at setpoint temperature 25ºC, the EUI value falls down as much as 21,43% (48 kWh/m2/tahun) and when the setpoint temperature 25ºC set at the public area, EUI value drops 9,19% (21 kWh/m2/year) Using bigger chiller capacity, the setpoint temperature at public area often met unlike using one chiller only. text |
institution |
Institut Teknologi Bandung |
building |
Institut Teknologi Bandung Library |
continent |
Asia |
country |
Indonesia Indonesia |
content_provider |
Institut Teknologi Bandung |
collection |
Digital ITB |
language |
Indonesia |
topic |
Teknik (Rekayasa, enjinering dan kegiatan berkaitan) |
spellingShingle |
Teknik (Rekayasa, enjinering dan kegiatan berkaitan) Dwisstya Utami, Amanda IDENTIFICATION OF A HOTEL BUILDING ENERGY CONSERVATION OPPORTUNITIES IN BANDUNG |
description |
Hotel is one of an example of commercial buildings with high energy
consumption which caused by the customer’s demand of good service and
comfort while using the facility. Hence, this study is conducted to identify Energy
Conservation Opportunity (ECO) in a 4-star hotel building in Bandung to improve
the building energy performance. Evaluating EUI (Energy Use Intensity) is done
to achieve the objective. The lower EUI values, shows the better energy building
performance.
Evaluation of EUI value is done by simulation using Energyplus V8.4 software.
The result shows that the building actual condition has EUI value of 252,20
kWh/m2/year with the condition of temperature setpoint often not met. The
desired temperature setpoint is 19ºC while the room temperature shows higher
temperature. There are several parameters changed such as SC glass, temperature
setpoint, and doubled chiller capacity. The result shows that the most effective
energy saving method attained when chiller capacity increased and temperature
setpoint set higher. When the entire hotel area are set at setpoint temperature
25ºC, the EUI value falls down as much as 21,43% (48 kWh/m2/tahun) and when
the setpoint temperature 25ºC set at the public area, EUI value drops 9,19% (21
kWh/m2/year) Using bigger chiller capacity, the setpoint temperature at public
area often met unlike using one chiller only. |
format |
Final Project |
author |
Dwisstya Utami, Amanda |
author_facet |
Dwisstya Utami, Amanda |
author_sort |
Dwisstya Utami, Amanda |
title |
IDENTIFICATION OF A HOTEL BUILDING ENERGY CONSERVATION OPPORTUNITIES IN BANDUNG |
title_short |
IDENTIFICATION OF A HOTEL BUILDING ENERGY CONSERVATION OPPORTUNITIES IN BANDUNG |
title_full |
IDENTIFICATION OF A HOTEL BUILDING ENERGY CONSERVATION OPPORTUNITIES IN BANDUNG |
title_fullStr |
IDENTIFICATION OF A HOTEL BUILDING ENERGY CONSERVATION OPPORTUNITIES IN BANDUNG |
title_full_unstemmed |
IDENTIFICATION OF A HOTEL BUILDING ENERGY CONSERVATION OPPORTUNITIES IN BANDUNG |
title_sort |
identification of a hotel building energy conservation opportunities in bandung |
url |
https://digilib.itb.ac.id/gdl/view/44910 |
_version_ |
1822926967489429504 |