HIGH VOLTAGE POWER TRANSFORMER CONDITION ASSESSMENT CONSIDERING ITS HEALTH INDEX VALUE AND DECREASING RATE
Power transformer is one of the most important utilities that has a critical role in good electrical power delivery. Thus, its performance has to be assessed periodically to prevent failure. Then, the transformers will not suddenly fail. A health index method is a useful tool for the transformer...
Saved in:
Main Author: | |
---|---|
Format: | Theses |
Language: | Indonesia |
Online Access: | https://digilib.itb.ac.id/gdl/view/50499 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Institut Teknologi Bandung |
Language: | Indonesia |
Summary: | Power transformer is one of the most important utilities that has a critical role in
good electrical power delivery. Thus, its performance has to be assessed
periodically to prevent failure. Then, the transformers will not suddenly fail. A
health index method is a useful tool for the transformer assessment condition. This
method has been carried out in several previous studies. However, most of them
have not observed the health index decreasing rate as an aspect to improve the
transformer condition assessment. This study proposed a health index method with
different approaches, then consider the values and its decreasing rate to assess the
transformer condition.
This study involved inspection data from in-service and out-of-service 150 kV
power transformers provided by the Indonesian electric company. The correlation
between operating age to Health Index value and Health Index decreasing rate were
also observed. With increasing operation age, the Health Index value tends to be
decreasing with a correlation coefficient R2
0.631. Further analysis was done to
power transformers with historical data of 3 years or more, showing the tendency
of Health Index value decreasing rate is higher with older transformers. This paper
also illustrates the Health Index analysis of 35 out-of-service transformers, resulting
in more suitable HI value compared to the previous approach. After that, this study
proposed the transformer risk assessment based on its health index value and the
decreasing rate. |
---|