IMPACT OF SOLAR PV-BATTERY SYSTEM TO APPROACH NET ZERO ENERGY BUILDING BASED ON PMV
Heating, Ventilating, and Air Conditioning (HVAC) systems takes large part of electrical consumption in building particularly if temperature setpoint is cold in long duration. Therefore, controlling HVAC is important to reduce power consumption. But, reducing temperature can change thermal comfor...
Saved in:
Main Author: | |
---|---|
Format: | Final Project |
Language: | Indonesia |
Online Access: | https://digilib.itb.ac.id/gdl/view/55251 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Institut Teknologi Bandung |
Language: | Indonesia |
id |
id-itb.:55251 |
---|---|
spelling |
id-itb.:552512021-06-16T15:40:07ZIMPACT OF SOLAR PV-BATTERY SYSTEM TO APPROACH NET ZERO ENERGY BUILDING BASED ON PMV Ulya Salmiya, Fatima Indonesia Final Project Predicted Mean Vote (PMV); Net Zero Energy Building; Solar PV; HVAC systems; Load Matching and Grid Interaction (LMGI); eQUEST; Python INSTITUT TEKNOLOGI BANDUNG https://digilib.itb.ac.id/gdl/view/55251 Heating, Ventilating, and Air Conditioning (HVAC) systems takes large part of electrical consumption in building particularly if temperature setpoint is cold in long duration. Therefore, controlling HVAC is important to reduce power consumption. But, reducing temperature can change thermal comfort in a building. There is an alternatives to keep thermal comfort by maintaining Predicted Mean Vote (PMV) at certain values. PMV values is optimized from HVAC usage in setpoint 18?C. PMV is optimized by changing setpoint hourly until PMV reached best range according to ASHRAE recommendation. This method can decrease HVAC usage so the total load is decreasing 114 kWh in a year. Optimized demand is used to model electricity system in building and measuring the Net Zero Energy (NZE) level. NZE level is calculated using balance graphs and Load Matching and Grid Interaction (LMGI) method. Variation in system are charging limit from grid with value of 95% and 65%, battery capacity with value of 1000 Ah and 1200 Ah, and PV capacity with value of 3 kW and 5 kW. A system with PV capacity 4 kW, battery capacity 900 Ah, and charging limit 80% is used as base case. Results show that the best system configuration to achieve NZE is system with PV capacity 4 kW, battery capacity 900 Ah, and charging limit 95%. This system has LOLP index 50.41%, LM 84.12%, NGI 49.59%, and exported energy reaching 1.215 MWh in a year. To achieve NZE, it is suggested to use the calculated capacity of PV and battery capacity and increasing charging limit in the optimum point from grid because energy exported from PV is higher. Demand variation shows that clothing insulation has higher standard deviation that occupancy. Building model is done using eQUEST while the electricity model is using Python. text |
institution |
Institut Teknologi Bandung |
building |
Institut Teknologi Bandung Library |
continent |
Asia |
country |
Indonesia Indonesia |
content_provider |
Institut Teknologi Bandung |
collection |
Digital ITB |
language |
Indonesia |
description |
Heating, Ventilating, and Air Conditioning (HVAC) systems takes large part of electrical
consumption in building particularly if temperature setpoint is cold in long duration. Therefore,
controlling HVAC is important to reduce power consumption. But, reducing temperature can
change thermal comfort in a building. There is an alternatives to keep thermal comfort by
maintaining Predicted Mean Vote (PMV) at certain values. PMV values is optimized from HVAC
usage in setpoint 18?C. PMV is optimized by changing setpoint hourly until PMV reached best
range according to ASHRAE recommendation. This method can decrease HVAC usage so the
total load is decreasing 114 kWh in a year. Optimized demand is used to model electricity system
in building and measuring the Net Zero Energy (NZE) level. NZE level is calculated using
balance graphs and Load Matching and Grid Interaction (LMGI) method. Variation in system
are charging limit from grid with value of 95% and 65%, battery capacity with value of 1000 Ah
and 1200 Ah, and PV capacity with value of 3 kW and 5 kW. A system with PV capacity 4 kW,
battery capacity 900 Ah, and charging limit 80% is used as base case. Results show that the best
system configuration to achieve NZE is system with PV capacity 4 kW, battery capacity 900 Ah,
and charging limit 95%. This system has LOLP index 50.41%, LM 84.12%, NGI 49.59%, and
exported energy reaching 1.215 MWh in a year. To achieve NZE, it is suggested to use the
calculated capacity of PV and battery capacity and increasing charging limit in the optimum
point from grid because energy exported from PV is higher. Demand variation shows that
clothing insulation has higher standard deviation that occupancy. Building model is done using
eQUEST while the electricity model is using Python. |
format |
Final Project |
author |
Ulya Salmiya, Fatima |
spellingShingle |
Ulya Salmiya, Fatima IMPACT OF SOLAR PV-BATTERY SYSTEM TO APPROACH NET ZERO ENERGY BUILDING BASED ON PMV |
author_facet |
Ulya Salmiya, Fatima |
author_sort |
Ulya Salmiya, Fatima |
title |
IMPACT OF SOLAR PV-BATTERY SYSTEM TO APPROACH NET ZERO ENERGY BUILDING BASED ON PMV |
title_short |
IMPACT OF SOLAR PV-BATTERY SYSTEM TO APPROACH NET ZERO ENERGY BUILDING BASED ON PMV |
title_full |
IMPACT OF SOLAR PV-BATTERY SYSTEM TO APPROACH NET ZERO ENERGY BUILDING BASED ON PMV |
title_fullStr |
IMPACT OF SOLAR PV-BATTERY SYSTEM TO APPROACH NET ZERO ENERGY BUILDING BASED ON PMV |
title_full_unstemmed |
IMPACT OF SOLAR PV-BATTERY SYSTEM TO APPROACH NET ZERO ENERGY BUILDING BASED ON PMV |
title_sort |
impact of solar pv-battery system to approach net zero energy building based on pmv |
url |
https://digilib.itb.ac.id/gdl/view/55251 |
_version_ |
1822929853939187712 |