OPTIMIZATION OF DISTRICT COOLING SYSTEM DESIGN FOR RESIDENTIAL DISTRICT IN INDONESIAâS NEW CAPITAL
Currently, the use of air conditioning systems in Indonesia is increasing. This increase also results in an increase in building electrical energy consumption. Meanwhile, most of the electricity production in Indonesia still relies on coal-fired power plants. Burning coal itself produces greenhou...
Saved in:
Main Author: | |
---|---|
Format: | Final Project |
Language: | Indonesia |
Online Access: | https://digilib.itb.ac.id/gdl/view/68959 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Institut Teknologi Bandung |
Language: | Indonesia |
id |
id-itb.:68959 |
---|---|
spelling |
id-itb.:689592022-09-19T15:43:12ZOPTIMIZATION OF DISTRICT COOLING SYSTEM DESIGN FOR RESIDENTIAL DISTRICT IN INDONESIAâS NEW CAPITAL Khulafa Laksana, Afrendi Indonesia Final Project district cooling, optimization, electricity consumption, life cycle cost INSTITUT TEKNOLOGI BANDUNG https://digilib.itb.ac.id/gdl/view/68959 Currently, the use of air conditioning systems in Indonesia is increasing. This increase also results in an increase in building electrical energy consumption. Meanwhile, most of the electricity production in Indonesia still relies on coal-fired power plants. Burning coal itself produces greenhouse gas emissions that are harmful to the environment. Therefore, an efficient air conditioning system is a must to reduce the required electricity consumption. A system that is considered efficient is the district cooling system. In a previous study, a comparison was made between individual air conditioning and district cooling air conditioning systems. Although the results have been obtained that the district cooling system is more efficient than the individual system, design development still needs to be tried in order to obtain a design with the minimum electrical energy consumption and life cycle costs as possible. So, this study presented an optimization of the district cooling design. Optimization was executed by reselecting the air handling unit and redesigning the central cooling plant. Furthermore, dividing each zone into several subclusters and re-designing the piping system diameter were also applied to sizing the characteristic of the optimum pump. Based on the initial design, the calculated district cooling electricity consumption and the 25 years life cycle costs were 50,955,007 kWh/year and IDR 1,967,624,826,071.00, respectively. Meanwhile, after central chillers resizing and piping system optimization, the estimated electricity consumption reduced to 47,205,485 kWh/year with the 25 years life cycle cost of IDR 1,810,202,254,509.00. Thus, the design optimization was successfully executed with an electrical energy consumption efficiency of 7.36% and cost efficiency of 8.00%. text |
institution |
Institut Teknologi Bandung |
building |
Institut Teknologi Bandung Library |
continent |
Asia |
country |
Indonesia Indonesia |
content_provider |
Institut Teknologi Bandung |
collection |
Digital ITB |
language |
Indonesia |
description |
Currently, the use of air conditioning systems in Indonesia is increasing. This
increase also results in an increase in building electrical energy consumption. Meanwhile,
most of the electricity production in Indonesia still relies on coal-fired power plants.
Burning coal itself produces greenhouse gas emissions that are harmful to the environment.
Therefore, an efficient air conditioning system is a must to reduce the required electricity
consumption. A system that is considered efficient is the district cooling system.
In a previous study, a comparison was made between individual air conditioning and
district cooling air conditioning systems. Although the results have been obtained that the
district cooling system is more efficient than the individual system, design development
still needs to be tried in order to obtain a design with the minimum electrical energy
consumption and life cycle costs as possible. So, this study presented an optimization of the
district cooling design. Optimization was executed by reselecting the air handling unit and
redesigning the central cooling plant. Furthermore, dividing each zone into several subclusters
and re-designing the piping system diameter were also applied to sizing the
characteristic of the optimum pump.
Based on the initial design, the calculated district cooling electricity consumption and
the 25 years life cycle costs were 50,955,007 kWh/year and IDR 1,967,624,826,071.00,
respectively. Meanwhile, after central chillers resizing and piping system optimization, the
estimated electricity consumption reduced to 47,205,485 kWh/year with the 25 years life
cycle cost of IDR 1,810,202,254,509.00. Thus, the design optimization was successfully
executed with an electrical energy consumption efficiency of 7.36% and cost efficiency of
8.00%. |
format |
Final Project |
author |
Khulafa Laksana, Afrendi |
spellingShingle |
Khulafa Laksana, Afrendi OPTIMIZATION OF DISTRICT COOLING SYSTEM DESIGN FOR RESIDENTIAL DISTRICT IN INDONESIAâS NEW CAPITAL |
author_facet |
Khulafa Laksana, Afrendi |
author_sort |
Khulafa Laksana, Afrendi |
title |
OPTIMIZATION OF DISTRICT COOLING SYSTEM DESIGN FOR RESIDENTIAL DISTRICT IN INDONESIAâS NEW CAPITAL |
title_short |
OPTIMIZATION OF DISTRICT COOLING SYSTEM DESIGN FOR RESIDENTIAL DISTRICT IN INDONESIAâS NEW CAPITAL |
title_full |
OPTIMIZATION OF DISTRICT COOLING SYSTEM DESIGN FOR RESIDENTIAL DISTRICT IN INDONESIAâS NEW CAPITAL |
title_fullStr |
OPTIMIZATION OF DISTRICT COOLING SYSTEM DESIGN FOR RESIDENTIAL DISTRICT IN INDONESIAâS NEW CAPITAL |
title_full_unstemmed |
OPTIMIZATION OF DISTRICT COOLING SYSTEM DESIGN FOR RESIDENTIAL DISTRICT IN INDONESIAâS NEW CAPITAL |
title_sort |
optimization of district cooling system design for residential district in indonesiaâs new capital |
url |
https://digilib.itb.ac.id/gdl/view/68959 |
_version_ |
1822278360023171072 |