DESIGN OF CLEAN WATER PLUMBING SYSTEM, WASTE WATER, VENT PIPE, RAINWATER, AND FIRE FIGHTING SYSTEM FOR CO-HOUSING FOR MILLENNIALS IN SOUTH TANGERANG
Co-housing for the Millennial Generation is a residential complex that combines several aspects and facilities in one place. In addition to residential units, in this Co-Housing for Millennial Generation there are various facilities that are currently important for some people, especially for mil...
Saved in:
Main Author: | |
---|---|
Format: | Final Project |
Language: | Indonesia |
Online Access: | https://digilib.itb.ac.id/gdl/view/78335 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Institut Teknologi Bandung |
Language: | Indonesia |
Summary: | Co-housing for the Millennial Generation is a residential complex that
combines several aspects and facilities in one place. In addition to residential units, in
this Co-Housing for Millennial Generation there are various facilities that are
currently important for some people, especially for millennial generation workers.
Several facilities such as sports fields, auditoriums, retail, and parks are available in
this residential complex. Built on an area of 1.2 hectares, it consists of four main towers
as residential units that also have 12 floors in them. Co-Housing for the Millennial
Generation is located on Jalan Pahlawan Seribu, Lengkong Gudang, Serpong District,
South Tangerang City. To provide the sanitation needs of this residential complex, the
design of the plumbing system is carried out to provide comfort for residents and
visitors to this building. The design of the plumbing system starts from the provision of
clean water, wastewater, vent, and rainwater to the fire fighting system. The design is
based on secondary data from several pieces of literature and sources, such as building
designer architects, design standard documents, and other design literature. The clean
water system uses water from PDAM sourced from PDAM Tirta Kerta Raharja with
the total demand of the four towers being 843.7 m³/day which produces blackwater
wastewater generation of 209.24 m³/day and greywater generation of 465.72 m³/day
which will then be processed for toilet flushing needs. The ven system uses a circuit
ven system that serves several plumbing devices simultaneously. The rainwater system
captures water away from the roof of the building and some other captures and then
accommodates building maintenance activities. The fire extinguishing system uses
automatic sprinkler systems, hydrants, and light fire extinguishers (APAR).
|
---|