ANALYSIS OF ACCURACY IMPROVEMENT IN ADAPTIVE AUTORECLOSE BASED ON TRAVELING WAVE IN HYBRID TRANSMISSION LINES

The 150 kV South Sumatra-Muntok hybrid transmission interconnection system utilizes a combination of various transmission media, including 25.7 km of overhead transmission lines, 3.937 km of underground cables, and 36.1 km of submarine cables. With a total length of 65.76 km, the system adopts an...

Full description

Saved in:
Bibliographic Details
Main Author: Iswara Alison, Johan
Format: Theses
Language:Indonesia
Online Access:https://digilib.itb.ac.id/gdl/view/87423
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Institut Teknologi Bandung
Language: Indonesia
id id-itb.:87423
spelling id-itb.:874232025-01-29T14:36:20ZANALYSIS OF ACCURACY IMPROVEMENT IN ADAPTIVE AUTORECLOSE BASED ON TRAVELING WAVE IN HYBRID TRANSMISSION LINES Iswara Alison, Johan Indonesia Theses Traveling wave fault location, adaptive auto reclose INSTITUT TEKNOLOGI BANDUNG https://digilib.itb.ac.id/gdl/view/87423 The 150 kV South Sumatra-Muntok hybrid transmission interconnection system utilizes a combination of various transmission media, including 25.7 km of overhead transmission lines, 3.937 km of underground cables, and 36.1 km of submarine cables. With a total length of 65.76 km, the system adopts an adaptive auto-reclose protection system that relies on the Traveling wave Fault Location (TWFL) method, integrated with the 87L line current differential relay. The autoreclose function is disabled when faults occur in the underground/submarine cable (USC/UGC) segments due to the high likelihood of permanent faults that damage the cable’s insulation layer. In contrast, most faults in the Overhead Line (OHL) segments are transient, and thus, the auto-reclose function is only activated in the OHL segments. This thesis explores methods to enhance the accuracy of TWFL in fault location determination through the analysis of operational data and switching events. The study emphasizes that the system’s accuracy is highly dependent on the protection relay’s response speed and the optimization of the traveling wave line propagation time (TWLPT) and traveling wave cable propagation time (TWCPT) settings. The results indicate that by recalibrating the TWLPT and TWCPT to 344.5 ?s and 3.048 ?s, respectively, the fault distance reading error can be reduced to 0.085%, or approximately ±56 meters. This suggests that a fine-tuning analysis based on operational data can significantly improve the precision of fault locators, reducing the error rate from 11.81% to 0.085%. text
institution Institut Teknologi Bandung
building Institut Teknologi Bandung Library
continent Asia
country Indonesia
Indonesia
content_provider Institut Teknologi Bandung
collection Digital ITB
language Indonesia
description The 150 kV South Sumatra-Muntok hybrid transmission interconnection system utilizes a combination of various transmission media, including 25.7 km of overhead transmission lines, 3.937 km of underground cables, and 36.1 km of submarine cables. With a total length of 65.76 km, the system adopts an adaptive auto-reclose protection system that relies on the Traveling wave Fault Location (TWFL) method, integrated with the 87L line current differential relay. The autoreclose function is disabled when faults occur in the underground/submarine cable (USC/UGC) segments due to the high likelihood of permanent faults that damage the cable’s insulation layer. In contrast, most faults in the Overhead Line (OHL) segments are transient, and thus, the auto-reclose function is only activated in the OHL segments. This thesis explores methods to enhance the accuracy of TWFL in fault location determination through the analysis of operational data and switching events. The study emphasizes that the system’s accuracy is highly dependent on the protection relay’s response speed and the optimization of the traveling wave line propagation time (TWLPT) and traveling wave cable propagation time (TWCPT) settings. The results indicate that by recalibrating the TWLPT and TWCPT to 344.5 ?s and 3.048 ?s, respectively, the fault distance reading error can be reduced to 0.085%, or approximately ±56 meters. This suggests that a fine-tuning analysis based on operational data can significantly improve the precision of fault locators, reducing the error rate from 11.81% to 0.085%.
format Theses
author Iswara Alison, Johan
spellingShingle Iswara Alison, Johan
ANALYSIS OF ACCURACY IMPROVEMENT IN ADAPTIVE AUTORECLOSE BASED ON TRAVELING WAVE IN HYBRID TRANSMISSION LINES
author_facet Iswara Alison, Johan
author_sort Iswara Alison, Johan
title ANALYSIS OF ACCURACY IMPROVEMENT IN ADAPTIVE AUTORECLOSE BASED ON TRAVELING WAVE IN HYBRID TRANSMISSION LINES
title_short ANALYSIS OF ACCURACY IMPROVEMENT IN ADAPTIVE AUTORECLOSE BASED ON TRAVELING WAVE IN HYBRID TRANSMISSION LINES
title_full ANALYSIS OF ACCURACY IMPROVEMENT IN ADAPTIVE AUTORECLOSE BASED ON TRAVELING WAVE IN HYBRID TRANSMISSION LINES
title_fullStr ANALYSIS OF ACCURACY IMPROVEMENT IN ADAPTIVE AUTORECLOSE BASED ON TRAVELING WAVE IN HYBRID TRANSMISSION LINES
title_full_unstemmed ANALYSIS OF ACCURACY IMPROVEMENT IN ADAPTIVE AUTORECLOSE BASED ON TRAVELING WAVE IN HYBRID TRANSMISSION LINES
title_sort analysis of accuracy improvement in adaptive autoreclose based on traveling wave in hybrid transmission lines
url https://digilib.itb.ac.id/gdl/view/87423
_version_ 1822999942439895040