SIMULASI TINGKAT KEPERLUAN ENERGI TERMAL PADA RUANG KULIAH BANGUNAN JURUSAN TEKNIK FISIKA FAKULTAS TEKNIK UNIVERSITAS GADJAH MADA YOGYAKARTA MENGGUNAKAN SOFTWARE AUTODESK ECOTECT 2010
Department of Physics Engineering Building UGM with a land area of approximately 1743.102 m2 which is at -7.8 º latitude and longitude 110.4 º 30 º direction of north and a suburb of Yogyakarta. This study tried to simulate the thermal state of the lecture rooms on Department of Physics Engineeri...
Saved in:
Main Authors: | , |
---|---|
Format: | Theses and Dissertations NonPeerReviewed |
Published: |
[Yogyakarta] : Universitas Gadjah Mada
2013
|
Subjects: | |
Online Access: | https://repository.ugm.ac.id/124391/ http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=64513 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Universitas Gadjah Mada |
Summary: | Department of Physics Engineering Building UGM with a land area of
approximately 1743.102 m2 which is at -7.8 º latitude and longitude 110.4 º 30 º
direction of north and a suburb of Yogyakarta.
This study tried to simulate the thermal state of the lecture rooms on
Department of Physics Engineering Building, Gadjah Mada University
Yogyakarta which should be a lot of use of air conditioning machines, therefore
the need for simulation calculation of how much thermal energy needs by one -
each classroom in order to base policy building officials in regulating the use of
ventilation and air conditioning to create thermal comfort with high efficiency
using Autodesk Ecotect 2010 software.
The building is modeled to some zone system. Authors divide it by
functions in space. So that the total amount to 88 zone, while 7 pieces zone of
research, namely by TN 1, 2, 3, 4, Seminar, 6 and 7.
The order total thermal load on the overall thermal simulation lecture halls
namely: internal gain (2458.50 kWh), thermal conduction gain/ fabric gain
(1550.221 kWh), thermal convection gain/ indirect solar gain (404.945 kWh),
direct solar gain (348.918 kWh), ventilation gain (185.523 kWh) and inter-zonal
gain (0.13 kWh).
While the comparison of the total thermal load on each classroom is TN 6
(203.115 kWh), TN 2 (194.175 kWh), TN 3 (188.425 kWh), TN 1 (175.786
kWh), TN 7 (163.696 kWh), Seminar Room (153.778 kWh), and TN 4 (140.150
kWh). |
---|