PENGUJIAN ELEKTRIS PADA PERBAIKAN TRANSFORMATOR DAYA 3 FASA 13800 V/34500 V 14,7 MVA
A transformer is an electrical apparatus that can move or transfer electrical energi and converts electrical energy from one voltage level to another level trough the performance of a single magnetic coupling and is based on the priciple of electromagnetic induction. A transformer must be equipped w...
Saved in:
Main Authors: | , |
---|---|
Format: | Theses and Dissertations NonPeerReviewed |
Published: |
[Yogyakarta] : Universitas Gadjah Mada
2013
|
Subjects: | |
Online Access: | https://repository.ugm.ac.id/124889/ http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=65051 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Universitas Gadjah Mada |
id |
id-ugm-repo.124889 |
---|---|
record_format |
dspace |
spelling |
id-ugm-repo.1248892016-03-04T08:44:32Z https://repository.ugm.ac.id/124889/ PENGUJIAN ELEKTRIS PADA PERBAIKAN TRANSFORMATOR DAYA 3 FASA 13800 V/34500 V 14,7 MVA , YANITA AYUNINGTYAS , Ir. Y. Wahyo Setiyono., MT. ETD A transformer is an electrical apparatus that can move or transfer electrical energi and converts electrical energy from one voltage level to another level trough the performance of a single magnetic coupling and is based on the priciple of electromagnetic induction. A transformer must be equipped with their nameplate. According to ANSI and IEEE commissioning a transformer at the time (the handover) should be tested first technical specifications listed on their nameplate. On occassion this intern authors conducted a final project in the form of case studies on the electrical checks on the three phase transformer with 13800 volts of primary voltage, secondary voltage of 34500 volts, and has a 14.7 MVA. After the repaired transformer needs to be done due diligence, process measurements taken include insulation resistance measurement, resistance measurement, measurement of the ratio, vector group testing, short circuit testing, and testing SFRA. Measurements were taken before the repair and after repair is completed. So that the results of these measurements can determine wheter or not a transformer is to be reused as the previous function. In the process of this measurement using the standard of Electrical Apparatus Service Association (EASA). [Yogyakarta] : Universitas Gadjah Mada 2013 Thesis NonPeerReviewed , YANITA AYUNINGTYAS and , Ir. Y. Wahyo Setiyono., MT. (2013) PENGUJIAN ELEKTRIS PADA PERBAIKAN TRANSFORMATOR DAYA 3 FASA 13800 V/34500 V 14,7 MVA. UNSPECIFIED thesis, UNSPECIFIED. http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=65051 |
institution |
Universitas Gadjah Mada |
building |
UGM Library |
country |
Indonesia |
collection |
Repository Civitas UGM |
topic |
ETD |
spellingShingle |
ETD , YANITA AYUNINGTYAS , Ir. Y. Wahyo Setiyono., MT. PENGUJIAN ELEKTRIS PADA PERBAIKAN TRANSFORMATOR DAYA 3 FASA 13800 V/34500 V 14,7 MVA |
description |
A transformer is an electrical apparatus that can move or transfer electrical
energi and converts electrical energy from one voltage level to another level
trough the performance of a single magnetic coupling and is based on the priciple
of electromagnetic induction. A transformer must be equipped with their
nameplate. According to ANSI and IEEE commissioning a transformer at the time
(the handover) should be tested first technical specifications listed on their
nameplate.
On occassion this intern authors conducted a final project in the form of
case studies on the electrical checks on the three phase transformer with 13800
volts of primary voltage, secondary voltage of 34500 volts, and has a 14.7 MVA.
After the repaired transformer needs to be done due diligence, process
measurements taken include insulation resistance measurement, resistance
measurement, measurement of the ratio, vector group testing, short circuit testing,
and testing SFRA. Measurements were taken before the repair and after repair is
completed. So that the results of these measurements can determine wheter or not
a transformer is to be reused as the previous function. In the process of this
measurement using the standard of Electrical Apparatus Service Association
(EASA). |
format |
Theses and Dissertations NonPeerReviewed |
author |
, YANITA AYUNINGTYAS , Ir. Y. Wahyo Setiyono., MT. |
author_facet |
, YANITA AYUNINGTYAS , Ir. Y. Wahyo Setiyono., MT. |
author_sort |
, YANITA AYUNINGTYAS |
title |
PENGUJIAN ELEKTRIS PADA PERBAIKAN TRANSFORMATOR DAYA 3 FASA 13800 V/34500 V 14,7 MVA |
title_short |
PENGUJIAN ELEKTRIS PADA PERBAIKAN TRANSFORMATOR DAYA 3 FASA 13800 V/34500 V 14,7 MVA |
title_full |
PENGUJIAN ELEKTRIS PADA PERBAIKAN TRANSFORMATOR DAYA 3 FASA 13800 V/34500 V 14,7 MVA |
title_fullStr |
PENGUJIAN ELEKTRIS PADA PERBAIKAN TRANSFORMATOR DAYA 3 FASA 13800 V/34500 V 14,7 MVA |
title_full_unstemmed |
PENGUJIAN ELEKTRIS PADA PERBAIKAN TRANSFORMATOR DAYA 3 FASA 13800 V/34500 V 14,7 MVA |
title_sort |
pengujian elektris pada perbaikan transformator daya 3 fasa 13800 v/34500 v 14,7 mva |
publisher |
[Yogyakarta] : Universitas Gadjah Mada |
publishDate |
2013 |
url |
https://repository.ugm.ac.id/124889/ http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=65051 |
_version_ |
1681232162813116416 |