STUDI EKSPERIMENTAL, PENGARUH APLIKASI LIQUID TO SUCTION HEAT EXCHANGER TERHADAP KINERJA SISTEM REFRIGERASI DENGAN REFRIGERAN R 404 A
Study of performance improvement of refrigeration systems with the R404a refrigerant have been experimentally studied using a liquid to suction heat exchanger (LSHX). The use of three LSH X�s wich having each area of heat transfer 62.80 cm 2 , 75.97 cm 2 and 151.94 cm 2 is to test the system with...
Saved in:
Main Authors: | , |
---|---|
Format: | Theses and Dissertations NonPeerReviewed |
Published: |
[Yogyakarta] : Universitas Gadjah Mada
2011
|
Subjects: | |
Online Access: | https://repository.ugm.ac.id/89167/ http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=51381 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Universitas Gadjah Mada |
Summary: | Study of performance improvement of refrigeration systems with the R404a
refrigerant have been experimentally studied using a liquid to suction heat
exchanger (LSHX). The use of three LSH X�s wich having each area of heat
transfer 62.80 cm
2
, 75.97 cm
2
and 151.94 cm
2
is to test the system with and
without LSHX at the cabin temperature setting 0°C,-10 °C and -20°C. The
results of tests showed that each LSHX has heat exchange effectiveness in
average of 0.35, 0.45 and 0.58. The effect of LSHX usage at refrigeration system
is to increase the Coefficient of Performance (COP) with the highest increase in
LSHX-1
st
application which has the highest. Tests also showed that the LSHX
application at low temperature settings (-10 °C and -20
o
C) increase the cooling
capacity, with the highest increasing in LSHX-2
nd
with the medium effectiveness.
While the achievement of temperature setting (chilling time) testing with LSHX
is longer compared to test without LSHX, with the longest average time
achievement on the test with LSHX-2. |
---|