PENGARUH FILTER PASIF PADA JARINGAN TEGANGAN RENDAH AKIBAT PEMBEBANAN SISTEM PENGGERAK DENGAN KECEPATAN YANG DAPAT DIATUR
The quality of electrical power can be called good when current and voltage wave is in pure sinusoidal form, the phases differ from each other 180 degrees and the fundamental frequency is 50 Hertz. If does not sinusoidal form, it means there is a problem in electrical power it is the presence of har...
Saved in:
Main Authors: | , |
---|---|
Format: | Theses and Dissertations NonPeerReviewed |
Published: |
[Yogyakarta] : Universitas Gadjah Mada
2011
|
Subjects: | |
Online Access: | https://repository.ugm.ac.id/91016/ http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=52688 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Universitas Gadjah Mada |
Summary: | The quality of electrical power can be called good when current and voltage
wave is in pure sinusoidal form, the phases differ from each other 180 degrees and
the fundamental frequency is 50 Hertz. If does not sinusoidal form, it means there
is a problem in electrical power it is the presence of harmonics. The damage
waveform is generally triggered by non-linear loads, one of which is the Variable
Speed Drive (VSD). Harmonics generated by the VSD is very annoying when the
harmonics quantition exceeds the harmonics standards established by the IEEE
standard 519-1992.
This study aims to determine the effect of single-tuned passive filters to
reduce the current and voltage harmonics on a three-phase power grid by VSD
3kW with 1.5 kW induction motor. The design of passive filter was done based on
analyzed a quantity of harmonics in VSD when it was loaded by induction motor.
Based on the research results it can be seen that the single-tuned passive filters are
arranged three-phase star connection, it has a great influence in reducing the
harmonic current distortion. The rate voltage harmonics before and after the filter
installed does not exceed the allowable limit. But value of harmonic currents before
reinstalling the filter exceeds the allowable standard limits. At the time of VSD is
not loaded harmonic currents THDI = 70.4%, and when the load of induction motor
reached 4.8 N / m, the current harmonics THDI = 125%. When there are no load
after having installed the filter, the harmonic currents THDI 19.6%. When there is
full load the current harmonics is THDI = 34.2%. The use of filter absorb the
additional power of 24 watts. |
---|