ANALISIS HARMONIK AKIBAT BEBAN-BEBAN NON LINIER PADA GEDUNG PERKANTORAN TERHADAP RUGI DAYA SALURAN
Non-linear loads are loads that have non-sinusoidal waveforms due to harmonic currents generated by a variety of electronic equipment. Today, many office buildings use a variety of electronic devices that generate non-linear current, such as computers, printers, scanners, air conditioner, energy sav...
Saved in:
Main Authors: | , |
---|---|
Format: | Theses and Dissertations NonPeerReviewed |
Published: |
[Yogyakarta] : Universitas Gadjah Mada
2012
|
Subjects: | |
Online Access: | https://repository.ugm.ac.id/98921/ http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=55273 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Universitas Gadjah Mada |
id |
id-ugm-repo.98921 |
---|---|
record_format |
dspace |
spelling |
id-ugm-repo.989212016-03-04T08:49:25Z https://repository.ugm.ac.id/98921/ ANALISIS HARMONIK AKIBAT BEBAN-BEBAN NON LINIER PADA GEDUNG PERKANTORAN TERHADAP RUGI DAYA SALURAN , Winarso,ST , Dr. Eng. F. Danang Wijaya, S.T., M.T. ETD Non-linear loads are loads that have non-sinusoidal waveforms due to harmonic currents generated by a variety of electronic equipment. Today, many office buildings use a variety of electronic devices that generate non-linear current, such as computers, printers, scanners, air conditioner, energy saving lamps and other equipment. High content of harmonics in non-linear loads can cause reduce power quality of system such lower power factor, distorted voltage waveform, increasing power loss, excessive heating in transformers and inefficiency in electrical energy usage. This research objectives are investigating the value of THDv and THDi produced non-linear loads in office building and evaluating measurement result using standard IEEE standard 519-1992, and reducing harmonics value by installing passive harmonic filters on the bus or panel that has exceessive THDi or THDv. Finally comparison analysis of THDv, THDi, and power losses before and after the installation of passive harmonic filters was done. In this study, case study was done using Engineering Faculty building of UMP (FT -UMP) data. Based on measurement and simulation results using ETAP, it was kwon that several bus on FT-UMP building having THDi in the range of 18.64% - 29.45% and power factor values range from 0.62 - 0.87. Single-tuned filter then was designed to reduce harmonics value. Installation of filter designed improving THDi value to below 15% and a power factor above 0.9. [Yogyakarta] : Universitas Gadjah Mada 2012 Thesis NonPeerReviewed , Winarso,ST and , Dr. Eng. F. Danang Wijaya, S.T., M.T. (2012) ANALISIS HARMONIK AKIBAT BEBAN-BEBAN NON LINIER PADA GEDUNG PERKANTORAN TERHADAP RUGI DAYA SALURAN. UNSPECIFIED thesis, UNSPECIFIED. http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=55273 |
institution |
Universitas Gadjah Mada |
building |
UGM Library |
country |
Indonesia |
collection |
Repository Civitas UGM |
topic |
ETD |
spellingShingle |
ETD , Winarso,ST , Dr. Eng. F. Danang Wijaya, S.T., M.T. ANALISIS HARMONIK AKIBAT BEBAN-BEBAN NON LINIER PADA GEDUNG PERKANTORAN TERHADAP RUGI DAYA SALURAN |
description |
Non-linear loads are loads that have non-sinusoidal waveforms due to
harmonic currents generated by a variety of electronic equipment. Today, many
office buildings use a variety of electronic devices that generate non-linear current,
such as computers, printers, scanners, air conditioner, energy saving lamps and
other equipment. High content of harmonics in non-linear loads can cause reduce
power quality of system such lower power factor, distorted voltage waveform,
increasing power loss, excessive heating in transformers and inefficiency in
electrical energy usage.
This research objectives are investigating the value of THDv and THDi
produced non-linear loads in office building and evaluating measurement result
using standard IEEE standard 519-1992, and reducing harmonics value by
installing passive harmonic filters on the bus or panel that has exceessive THDi or
THDv. Finally comparison analysis of THDv, THDi, and power losses before and
after the installation of passive harmonic filters was done. In this study, case study
was done using Engineering Faculty building of UMP (FT -UMP) data.
Based on measurement and simulation results using ETAP, it was kwon that
several bus on FT-UMP building having THDi in the range of 18.64% - 29.45%
and power factor values range from 0.62 - 0.87. Single-tuned filter then was
designed to reduce harmonics value. Installation of filter designed improving THDi
value to below 15% and a power factor above 0.9. |
format |
Theses and Dissertations NonPeerReviewed |
author |
, Winarso,ST , Dr. Eng. F. Danang Wijaya, S.T., M.T. |
author_facet |
, Winarso,ST , Dr. Eng. F. Danang Wijaya, S.T., M.T. |
author_sort |
, Winarso,ST |
title |
ANALISIS HARMONIK AKIBAT BEBAN-BEBAN NON
LINIER PADA GEDUNG PERKANTORAN TERHADAP RUGI
DAYA SALURAN |
title_short |
ANALISIS HARMONIK AKIBAT BEBAN-BEBAN NON
LINIER PADA GEDUNG PERKANTORAN TERHADAP RUGI
DAYA SALURAN |
title_full |
ANALISIS HARMONIK AKIBAT BEBAN-BEBAN NON
LINIER PADA GEDUNG PERKANTORAN TERHADAP RUGI
DAYA SALURAN |
title_fullStr |
ANALISIS HARMONIK AKIBAT BEBAN-BEBAN NON
LINIER PADA GEDUNG PERKANTORAN TERHADAP RUGI
DAYA SALURAN |
title_full_unstemmed |
ANALISIS HARMONIK AKIBAT BEBAN-BEBAN NON
LINIER PADA GEDUNG PERKANTORAN TERHADAP RUGI
DAYA SALURAN |
title_sort |
analisis harmonik akibat beban-beban non
linier pada gedung perkantoran terhadap rugi
daya saluran |
publisher |
[Yogyakarta] : Universitas Gadjah Mada |
publishDate |
2012 |
url |
https://repository.ugm.ac.id/98921/ http://etd.ugm.ac.id/index.php?mod=penelitian_detail&sub=PenelitianDetail&act=view&typ=html&buku_id=55273 |
_version_ |
1681230448233021440 |