Energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the Penang state mosque

The manual operation of an ON/OFF controller that is being widely used in the air-cooled chiller of the air conditioning system is found to have resulted in a significant daily variation of electricity usage. As such, this study had aimed to investigate the effect from the application of a pre-pro...

Full description

Saved in:
Bibliographic Details
Main Authors: Hussin, Azman, Lim, Chin Haw, Salleh, Elias @ Ilias
Format: Article
Language:English
English
Published: Universiti Kebangsaan Malaysia 2020
Subjects:
Online Access:http://irep.iium.edu.my/87882/1/87882_Energy%20Consumption%20Control%20of%20An%20Air-Cooled%20Chiller_article.pdf
http://irep.iium.edu.my/87882/2/87882_Energy%20Consumption%20Control%20of%20An%20Air-Cooled%20Chiller_wos.pdf
http://irep.iium.edu.my/87882/
http://www.ukm.my/jkukm/wp-content/uploads/2020/3201/16.pdf
https://doi.org/10.17576/jkukm-2020-32(1)-16
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Universiti Islam Antarabangsa Malaysia
Language: English
English
id my.iium.irep.87882
record_format dspace
spelling my.iium.irep.878822021-01-18T08:09:06Z http://irep.iium.edu.my/87882/ Energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the Penang state mosque Hussin, Azman Lim, Chin Haw Salleh, Elias @ Ilias NA2542.35 Environmental aspect of architecture NA Architecture The manual operation of an ON/OFF controller that is being widely used in the air-cooled chiller of the air conditioning system is found to have resulted in a significant daily variation of electricity usage. As such, this study had aimed to investigate the effect from the application of a pre-programmed auto timer control system (ADTCS ON/OFF) on the performance of an air-cooled chiller and its main components in the Penang State Mosque. The ADTCS ON/OFF that had been developed for both the indoor and outdoor usage was installed to an existing air conditioning electrical distribution board (DB) via an external control panel, which had consisted of a selector switch with a timer operation, a power supply, an ON/OFF push button for the AHU, a lamp indicator as well as that of a digital timer (brand Honeywell HWTHC711A). Apart from demonstrating the implementation of the ADTCS ON/OFF control system as contributing to a more consistent operation time, this study had also shown the manual operation of the air-cooled chiller as contributing to an impactful loss of approximately 9.6 hours or 3182 kWh on a normal day when being compared to that of the ADTCS ON/OFF control system. Since the findings from this research had shown the use of an ADTCS ON/OFF control system in the air-cooled chiller system as providing a positive implication of the monthly electricity cost to the Penang State Mosque and the mosque institutions as a whole, this therefore suggests that a big savings of expenditure can also be achieved from the implementation of such a system. Universiti Kebangsaan Malaysia 2020 Article PeerReviewed application/pdf en http://irep.iium.edu.my/87882/1/87882_Energy%20Consumption%20Control%20of%20An%20Air-Cooled%20Chiller_article.pdf application/pdf en http://irep.iium.edu.my/87882/2/87882_Energy%20Consumption%20Control%20of%20An%20Air-Cooled%20Chiller_wos.pdf Hussin, Azman and Lim, Chin Haw and Salleh, Elias @ Ilias (2020) Energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the Penang state mosque. Jurnal Kejuruteraan, 32 (1). pp. 131-139. ISSN 0128-0198 E-ISSN 2289-7526 http://www.ukm.my/jkukm/wp-content/uploads/2020/3201/16.pdf https://doi.org/10.17576/jkukm-2020-32(1)-16
institution Universiti Islam Antarabangsa Malaysia
building IIUM Library
collection Institutional Repository
continent Asia
country Malaysia
content_provider International Islamic University Malaysia
content_source IIUM Repository (IREP)
url_provider http://irep.iium.edu.my/
language English
English
topic NA2542.35 Environmental aspect of architecture
NA Architecture
spellingShingle NA2542.35 Environmental aspect of architecture
NA Architecture
Hussin, Azman
Lim, Chin Haw
Salleh, Elias @ Ilias
Energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the Penang state mosque
description The manual operation of an ON/OFF controller that is being widely used in the air-cooled chiller of the air conditioning system is found to have resulted in a significant daily variation of electricity usage. As such, this study had aimed to investigate the effect from the application of a pre-programmed auto timer control system (ADTCS ON/OFF) on the performance of an air-cooled chiller and its main components in the Penang State Mosque. The ADTCS ON/OFF that had been developed for both the indoor and outdoor usage was installed to an existing air conditioning electrical distribution board (DB) via an external control panel, which had consisted of a selector switch with a timer operation, a power supply, an ON/OFF push button for the AHU, a lamp indicator as well as that of a digital timer (brand Honeywell HWTHC711A). Apart from demonstrating the implementation of the ADTCS ON/OFF control system as contributing to a more consistent operation time, this study had also shown the manual operation of the air-cooled chiller as contributing to an impactful loss of approximately 9.6 hours or 3182 kWh on a normal day when being compared to that of the ADTCS ON/OFF control system. Since the findings from this research had shown the use of an ADTCS ON/OFF control system in the air-cooled chiller system as providing a positive implication of the monthly electricity cost to the Penang State Mosque and the mosque institutions as a whole, this therefore suggests that a big savings of expenditure can also be achieved from the implementation of such a system.
format Article
author Hussin, Azman
Lim, Chin Haw
Salleh, Elias @ Ilias
author_facet Hussin, Azman
Lim, Chin Haw
Salleh, Elias @ Ilias
author_sort Hussin, Azman
title Energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the Penang state mosque
title_short Energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the Penang state mosque
title_full Energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the Penang state mosque
title_fullStr Energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the Penang state mosque
title_full_unstemmed Energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the Penang state mosque
title_sort energy consumption control of an air-cooled chiller from the use of an automatic on/off timer system: a real case study of the penang state mosque
publisher Universiti Kebangsaan Malaysia
publishDate 2020
url http://irep.iium.edu.my/87882/1/87882_Energy%20Consumption%20Control%20of%20An%20Air-Cooled%20Chiller_article.pdf
http://irep.iium.edu.my/87882/2/87882_Energy%20Consumption%20Control%20of%20An%20Air-Cooled%20Chiller_wos.pdf
http://irep.iium.edu.my/87882/
http://www.ukm.my/jkukm/wp-content/uploads/2020/3201/16.pdf
https://doi.org/10.17576/jkukm-2020-32(1)-16
_version_ 1690370775836524544