Corona fault detection in switchgear with extreme learning machine
Switchgear is a very important component in a power distribution line. Failure in switchgear can lead to catastrophic danger and losses. In this research, a fault detection system is proposed with the implementation of Extreme Learning Machine (ELM). This algorithm is capable to identify faults in s...
Saved in:
Main Authors: | , , , , |
---|---|
Other Authors: | |
Format: | Article |
Published: |
Institute of Advanced Engineering and Science
2023
|
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Universiti Tenaga Nasional |
Summary: | Switchgear is a very important component in a power distribution line. Failure in switchgear can lead to catastrophic danger and losses. In this research, a fault detection system is proposed with the implementation of Extreme Learning Machine (ELM). This algorithm is capable to identify faults in switchgear by analyzing the sound wave generated. Experiments are carried out to investigate the performance of the developed algorithm in identifying Corona faults in switchgears. The performances are analyzed in time and frequency domains, respectively. In time domain analysis, the results show 90.63%, 87.5%, and 87.5% of success rates in differentiating the Corona and non-Corona cases in training, validation and testing phases respectively. In frequency domain analysis, the results show 89.84%, 83.33%, and 87.5% success rates in training, validation and testing phases respectively. It can thus be concluded that the developed algorithm performed well in identifying Corona faults in switchgears. � 2020, Institute of Advanced Engineering and Science. All rights reserved. |
---|