Incipient fault detection in 33/11kV power transformers by using combined Dissolved Gas Analysis technique and acoustic partial discharge measurement and validated through untanking

Power transformer consists of components which are under consistent thermal and electrical stresses. The major component which degrades under these stresses is the paper insulation of the power transformer. The electrical fault can develop into thermal fault such as localized insulation burning or h...

Full description

Saved in:
Bibliographic Details
Main Authors: Samsudin M.R., Ramli A.Q., Berhanuddin A., Yang Y.Z.
Other Authors: 35410298500
Format: Conference paper
Published: 2023
Subjects:
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Universiti Tenaga Nasional
id my.uniten.dspace-30594
record_format dspace
spelling my.uniten.dspace-305942023-12-29T15:49:59Z Incipient fault detection in 33/11kV power transformers by using combined Dissolved Gas Analysis technique and acoustic partial discharge measurement and validated through untanking Samsudin M.R. Ramli A.Q. Berhanuddin A. Yang Y.Z. 35410298500 35779000400 35777444200 52664733400 Arcing Dissolved Gas Analysis On Load Tap Changer (OLTC) Partial Discharge Discharge (fluid mechanics) Dissolution Electric fault location Electric power systems Fault detection Gas chromatography Partial discharges Power transmission Surface discharges Thermal insulation Voltage control Arcing Choking effects Dissolved gas analysis Dissolved-gas-analysis techniques Electrical faults Electrical stress Hotspots Incipient fault detection Incipient faults On-load tap changers Paper insulation Partial discharge measurements Sharp edges Surface tracking Thermal faults Power transformers Power transformer consists of components which are under consistent thermal and electrical stresses. The major component which degrades under these stresses is the paper insulation of the power transformer. The electrical fault can develop into thermal fault such as localized insulation burning or hot-spots. Any fault in the transformer can be detected by using Dissolved Gas Analysis technique. In this paper, the detection of electrical and thermal faults in 14 units of 33/11kV, 30 MVA and 15MVA transformers were done by using Dissolved Gas Analysis (DGA). Then, the acoustic partial discharge test was carried out to detect the activity and locate the source of the electrical fault. All the transformers were untanked and the inspection was done. From the inspection done, there were a few incipient faults detected such as overheating due to loose connection, sharp edges, insulation burning, choking effect due to moisture and surface tracking in On-Load Tap Changer (OLTC) compartment. As a conclusion, the combination of the acoustic partial discharge technique and DGA technique have proved to be a useful tool in detecting and locating incipient faults in the power transformer. � 2011 Institute of Electrical Power. Final 2023-12-29T07:49:59Z 2023-12-29T07:49:59Z 2010 Conference paper 2-s2.0-80053102406 https://www.scopus.com/inward/record.uri?eid=2-s2.0-80053102406&partnerID=40&md5=05452646b918430c372da1d2f9f58fe7 https://irepository.uniten.edu.my/handle/123456789/30594 6007229 Scopus
institution Universiti Tenaga Nasional
building UNITEN Library
collection Institutional Repository
continent Asia
country Malaysia
content_provider Universiti Tenaga Nasional
content_source UNITEN Institutional Repository
url_provider http://dspace.uniten.edu.my/
topic Arcing
Dissolved Gas Analysis
On Load Tap Changer (OLTC)
Partial Discharge
Discharge (fluid mechanics)
Dissolution
Electric fault location
Electric power systems
Fault detection
Gas chromatography
Partial discharges
Power transmission
Surface discharges
Thermal insulation
Voltage control
Arcing
Choking effects
Dissolved gas analysis
Dissolved-gas-analysis techniques
Electrical faults
Electrical stress
Hotspots
Incipient fault detection
Incipient faults
On-load tap changers
Paper insulation
Partial discharge measurements
Sharp edges
Surface tracking
Thermal faults
Power transformers
spellingShingle Arcing
Dissolved Gas Analysis
On Load Tap Changer (OLTC)
Partial Discharge
Discharge (fluid mechanics)
Dissolution
Electric fault location
Electric power systems
Fault detection
Gas chromatography
Partial discharges
Power transmission
Surface discharges
Thermal insulation
Voltage control
Arcing
Choking effects
Dissolved gas analysis
Dissolved-gas-analysis techniques
Electrical faults
Electrical stress
Hotspots
Incipient fault detection
Incipient faults
On-load tap changers
Paper insulation
Partial discharge measurements
Sharp edges
Surface tracking
Thermal faults
Power transformers
Samsudin M.R.
Ramli A.Q.
Berhanuddin A.
Yang Y.Z.
Incipient fault detection in 33/11kV power transformers by using combined Dissolved Gas Analysis technique and acoustic partial discharge measurement and validated through untanking
description Power transformer consists of components which are under consistent thermal and electrical stresses. The major component which degrades under these stresses is the paper insulation of the power transformer. The electrical fault can develop into thermal fault such as localized insulation burning or hot-spots. Any fault in the transformer can be detected by using Dissolved Gas Analysis technique. In this paper, the detection of electrical and thermal faults in 14 units of 33/11kV, 30 MVA and 15MVA transformers were done by using Dissolved Gas Analysis (DGA). Then, the acoustic partial discharge test was carried out to detect the activity and locate the source of the electrical fault. All the transformers were untanked and the inspection was done. From the inspection done, there were a few incipient faults detected such as overheating due to loose connection, sharp edges, insulation burning, choking effect due to moisture and surface tracking in On-Load Tap Changer (OLTC) compartment. As a conclusion, the combination of the acoustic partial discharge technique and DGA technique have proved to be a useful tool in detecting and locating incipient faults in the power transformer. � 2011 Institute of Electrical Power.
author2 35410298500
author_facet 35410298500
Samsudin M.R.
Ramli A.Q.
Berhanuddin A.
Yang Y.Z.
format Conference paper
author Samsudin M.R.
Ramli A.Q.
Berhanuddin A.
Yang Y.Z.
author_sort Samsudin M.R.
title Incipient fault detection in 33/11kV power transformers by using combined Dissolved Gas Analysis technique and acoustic partial discharge measurement and validated through untanking
title_short Incipient fault detection in 33/11kV power transformers by using combined Dissolved Gas Analysis technique and acoustic partial discharge measurement and validated through untanking
title_full Incipient fault detection in 33/11kV power transformers by using combined Dissolved Gas Analysis technique and acoustic partial discharge measurement and validated through untanking
title_fullStr Incipient fault detection in 33/11kV power transformers by using combined Dissolved Gas Analysis technique and acoustic partial discharge measurement and validated through untanking
title_full_unstemmed Incipient fault detection in 33/11kV power transformers by using combined Dissolved Gas Analysis technique and acoustic partial discharge measurement and validated through untanking
title_sort incipient fault detection in 33/11kv power transformers by using combined dissolved gas analysis technique and acoustic partial discharge measurement and validated through untanking
publishDate 2023
_version_ 1806428381671063552