System-level experimental investigations of the direct immersion cooling data center units with thermodynamic and thermoeconomic assessments
The study is to perform thermodynamic, economic and thermoeconomic assessments for two different direct immersion cooling data center systems which are the single-phase and the two-phase immersion cooling systems with the operating ranges of 3.2–27.6 kW and 6.8–15.9 kW, respectively. The two-phase c...