Performance testing of vapor compression system of aircon system
This project describes the construction and performance testing of the vapor compression cycle (VCC). In addition to that, it also analyzes the various data collected and aims study the COP based on a fixed EEV opening degree and varying the compressor, condenser and evaporator fan frequency. Thi...
Saved in:
Main Author: | |
---|---|
Other Authors: | |
Format: | Final Year Project |
Language: | English |
Published: |
2010
|
Subjects: | |
Online Access: | http://hdl.handle.net/10356/40597 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Nanyang Technological University |
Language: | English |
id |
sg-ntu-dr.10356-40597 |
---|---|
record_format |
dspace |
spelling |
sg-ntu-dr.10356-405972023-07-07T16:37:18Z Performance testing of vapor compression system of aircon system Heng, Eugene Yi Jian. Cai Wenjian School of Electrical and Electronic Engineering DRNTU::Engineering::Electrical and electronic engineering This project describes the construction and performance testing of the vapor compression cycle (VCC). In addition to that, it also analyzes the various data collected and aims study the COP based on a fixed EEV opening degree and varying the compressor, condenser and evaporator fan frequency. This project uses R134a as the working refrigerant and the concept of multievaporators and EEVs integrated with the system. Firstly, the various components like the condensers, EEVs, evaporators and etc were put together to construct the system. Following that, various tests were carried out and analyzed before determining the range of COP. Studies has found out that the on-off cycling of the system causes the coefficient of performance (COP) to be below 75% of the steady-state values. The transient losses during cycling are mainly attributed to two different phenomena: thermodynamic losses (heat exchangers mass) and start/stop losses (refrigerant migration). Many studies have been done on refrigeration systems with single evaporator or single EEV but this is not the case for multi evaporators and EEVs [1]. The multievaporator air-conditioner (MEAC) consists of one compressor, one condenser, several evaporators and the same number of expansion valves [2]. In this project, the MEAC uses one compressor to drive several evaporators simultaneously therefore, its dynamics are more complicated than the single-evaporator machine [2]. It was found that the COP ranged from 2.66 to 3.85 and the performance was affected especially when the compressor frequency was changed. Bachelor of Engineering 2010-06-17T00:42:21Z 2010-06-17T00:42:21Z 2010 2010 Final Year Project (FYP) http://hdl.handle.net/10356/40597 en Nanyang Technological University 70 p. application/pdf |
institution |
Nanyang Technological University |
building |
NTU Library |
continent |
Asia |
country |
Singapore Singapore |
content_provider |
NTU Library |
collection |
DR-NTU |
language |
English |
topic |
DRNTU::Engineering::Electrical and electronic engineering |
spellingShingle |
DRNTU::Engineering::Electrical and electronic engineering Heng, Eugene Yi Jian. Performance testing of vapor compression system of aircon system |
description |
This project describes the construction and performance testing of the vapor compression cycle
(VCC). In addition to that, it also analyzes the various data collected and aims study the COP
based on a fixed EEV opening degree and varying the compressor, condenser and evaporator fan
frequency. This project uses R134a as the working refrigerant and the concept of multievaporators
and EEVs integrated with the system. Firstly, the various components like the
condensers, EEVs, evaporators and etc were put together to construct the system. Following that,
various tests were carried out and analyzed before determining the range of COP. Studies has
found out that the on-off cycling of the system causes the coefficient of performance (COP) to be
below 75% of the steady-state values. The transient losses during cycling are mainly attributed to
two different phenomena: thermodynamic losses (heat exchangers mass) and start/stop losses
(refrigerant migration). Many studies have been done on refrigeration systems with single
evaporator or single EEV but this is not the case for multi evaporators and EEVs [1]. The multievaporator
air-conditioner (MEAC) consists of one compressor, one condenser, several
evaporators and the same number of expansion valves [2]. In this project, the MEAC uses one
compressor to drive several evaporators simultaneously therefore, its dynamics are more
complicated than the single-evaporator machine [2]. It was found that the COP ranged from 2.66
to 3.85 and the performance was affected especially when the compressor frequency was
changed. |
author2 |
Cai Wenjian |
author_facet |
Cai Wenjian Heng, Eugene Yi Jian. |
format |
Final Year Project |
author |
Heng, Eugene Yi Jian. |
author_sort |
Heng, Eugene Yi Jian. |
title |
Performance testing of vapor compression system of aircon system |
title_short |
Performance testing of vapor compression system of aircon system |
title_full |
Performance testing of vapor compression system of aircon system |
title_fullStr |
Performance testing of vapor compression system of aircon system |
title_full_unstemmed |
Performance testing of vapor compression system of aircon system |
title_sort |
performance testing of vapor compression system of aircon system |
publishDate |
2010 |
url |
http://hdl.handle.net/10356/40597 |
_version_ |
1772828693097349120 |