Equipment diagnostic audit for energy management of central air conditioning systems
This project aims at developing an equipment diagnostic audit (EDA) model to identify such deficiency with the objective of optimizing overall system efficiency. The EDA model was built based on actual data obtained from a real CACS, the North Spine central air conditioning plant of NTU with an inst...
Saved in:
Main Authors: | , |
---|---|
Other Authors: | |
Format: | Research Report |
Published: |
2008
|
Subjects: | |
Online Access: | http://hdl.handle.net/10356/7009 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Nanyang Technological University |
id |
sg-ntu-dr.10356-7009 |
---|---|
record_format |
dspace |
spelling |
sg-ntu-dr.10356-70092023-03-04T18:06:08Z Equipment diagnostic audit for energy management of central air conditioning systems Tay, Seow Ngie Kah, Yin Muk School of Mechanical and Aerospace Engineering DRNTU::Engineering::Mechanical engineering::Energy conservation This project aims at developing an equipment diagnostic audit (EDA) model to identify such deficiency with the objective of optimizing overall system efficiency. The EDA model was built based on actual data obtained from a real CACS, the North Spine central air conditioning plant of NTU with an installed cooling capacity of 3500 RT serving a total air conditioning floor area of 50,700 m2. The EDA model has proven to be an effective tool in diagnosing the key factors contributing to inefficiency in chiller plant. Through the application of the EDA procedure, the inefficient operational practices were eliminated and the efficiency of the North Spine CACS had improved drastically since May 2001. This is reflected in the drop in weekly electricity consumption of the plant from 190,000 kWh per week in May 2001 to 110,000 kWh per week in May 2004. 2008-09-18T05:58:53Z 2008-09-18T05:58:53Z 2005 2005 Research Report http://hdl.handle.net/10356/7009 Nanyang Technological University application/pdf |
institution |
Nanyang Technological University |
building |
NTU Library |
continent |
Asia |
country |
Singapore Singapore |
content_provider |
NTU Library |
collection |
DR-NTU |
topic |
DRNTU::Engineering::Mechanical engineering::Energy conservation |
spellingShingle |
DRNTU::Engineering::Mechanical engineering::Energy conservation Tay, Seow Ngie Kah, Yin Muk Equipment diagnostic audit for energy management of central air conditioning systems |
description |
This project aims at developing an equipment diagnostic audit (EDA) model to identify such deficiency with the objective of optimizing overall system efficiency. The EDA model was built based on actual data obtained from a real CACS, the North Spine central air conditioning plant of NTU with an installed cooling capacity of 3500 RT serving a total air conditioning floor area of 50,700 m2. The EDA model has proven to be an effective tool in diagnosing the key factors contributing to inefficiency in chiller plant. Through the application of the EDA procedure, the inefficient operational practices were eliminated and the efficiency of the North Spine CACS had improved drastically since May 2001. This is reflected in the drop in weekly electricity consumption of the plant from 190,000 kWh per week in May 2001 to 110,000 kWh per week in May 2004. |
author2 |
School of Mechanical and Aerospace Engineering |
author_facet |
School of Mechanical and Aerospace Engineering Tay, Seow Ngie Kah, Yin Muk |
format |
Research Report |
author |
Tay, Seow Ngie Kah, Yin Muk |
author_sort |
Tay, Seow Ngie |
title |
Equipment diagnostic audit for energy management of central air conditioning systems |
title_short |
Equipment diagnostic audit for energy management of central air conditioning systems |
title_full |
Equipment diagnostic audit for energy management of central air conditioning systems |
title_fullStr |
Equipment diagnostic audit for energy management of central air conditioning systems |
title_full_unstemmed |
Equipment diagnostic audit for energy management of central air conditioning systems |
title_sort |
equipment diagnostic audit for energy management of central air conditioning systems |
publishDate |
2008 |
url |
http://hdl.handle.net/10356/7009 |
_version_ |
1759853388675153920 |