Experimental study on a multi-evaporator refrigeration system with variable area ratio ejector

This paper describes an experimental study on a multi-evaporator refrigeration system (MERS) with conventional pressure regulating valve (PRV) and variable area ratio ejector. Some key performance indicators such as cooling capacity, power consumption and ejector entrainment ratio were evaluated by...

Full description

Saved in:
Bibliographic Details
Main Authors: Li, Cui, Yan, Jia, Li, Yanzhong, Cai, Wenjian, Lin, Chen, Chen, Haoran
Other Authors: School of Electrical and Electronic Engineering
Format: Article
Language:English
Published: 2017
Subjects:
Online Access:https://hdl.handle.net/10356/85017
http://hdl.handle.net/10220/42089
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Nanyang Technological University
Language: English
Description
Summary:This paper describes an experimental study on a multi-evaporator refrigeration system (MERS) with conventional pressure regulating valve (PRV) and variable area ratio ejector. Some key performance indicators such as cooling capacity, power consumption and ejector entrainment ratio were evaluated by switching operating modes, adjusting superheat and tuning ejector spindle and so on. The results indicated that: (1) the energy efficiency of the MERS can be improved by up to 12% by replacing the conventional pressure regulating valve with the variable area ratio ejector, (2) sufficient superheat or superheat degree greater than 2 °C is conducive to high entrainment performance of the ejector, large cooling capacity of the low-temperature evaporator and low power consumption of the system, and (3) the effect of nozzle spindle position on the performance of the system is evident.