Effects of airflow rate and supply air temperature on the airflow pattern under active chilled beam system

Effects of airflow rate and supply air temperature on the airflow pattern for Active Chilled Beams (ACB) system are investigated in this paper. The air velocity for the air jet near the ceiling are tested and recorded under both isothermal and non-isothermal conditions. The self-similarity for the a...

Full description

Saved in:
Bibliographic Details
Main Authors: Wu, Bingjie, Cai, Wenjian, Chen, Haoran
Other Authors: School of Electrical and Electronic Engineering
Format: Conference or Workshop Item
Language:English
Published: 2019
Subjects:
Online Access:https://hdl.handle.net/10356/88346
http://hdl.handle.net/10220/47628
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Nanyang Technological University
Language: English
Description
Summary:Effects of airflow rate and supply air temperature on the airflow pattern for Active Chilled Beams (ACB) system are investigated in this paper. The air velocity for the air jet near the ceiling are tested and recorded under both isothermal and non-isothermal conditions. The self-similarity for the air jet is observed to be feasible for a certain downstream distance where the vertical maximum velocity is within 1.25 slot heights. A comparison study has been conducted for two mathematical models describing the self-similarity with the experimental data. It turns out that Verhoff’s model has an overall better performance than Schwarz and Cosart’s model.