A simple test to confirm control valve stiction

Stiction is a common problem in the widely used spring-diaphragm type control valves in the process industry. Several methods are available for detecting stiction in control valves. After detection of stiction, a test is required to confirm that the valve in question is indeed suffering from stictio...

Full description

Saved in:
Bibliographic Details
Main Authors: Shah, Sirish L., Choudhury, M. A. A. Shoukat, Kariwala, Vinay, Douke, Hisato, Takada, Haruo
Other Authors: School of Chemical and Biomedical Engineering
Format: Conference or Workshop Item
Language:English
Published: 2009
Subjects:
Online Access:https://hdl.handle.net/10356/91281
http://hdl.handle.net/10220/6032
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Nanyang Technological University
Language: English
Description
Summary:Stiction is a common problem in the widely used spring-diaphragm type control valves in the process industry. Several methods are available for detecting stiction in control valves. After detection of stiction, a test is required to confirm that the valve in question is indeed suffering from stiction. This paper presents a simple closed loop test, based on changing only the controller gain, for confirming the presence of stiction. The method does not require that the loop be put in manual, which can otherwise upset the plant. The usefulness of this test is demonstrated through simulation studies and an industrial application.