Implementation of shunt active power filter using source voltage and source current detection

This paper presents the implementation of shunt active power filter using source voltage and source current detection. The harmonic current and reactive power compensation of shunt active power filter controller is based on the digital signal processing (DSP) to control its operation. First, the sig...

Full description

Saved in:
Bibliographic Details
Main Authors: Khruathep U., Premrudeepreechacharn S., Kumsuwan Y.
Format: Conference or Workshop Item
Language:English
Published: 2014
Online Access:http://www.scopus.com/inward/record.url?eid=2-s2.0-51949089148&partnerID=40&md5=b591d8883417b983f3b97adcf5fa874a
http://cmuir.cmu.ac.th/handle/6653943832/1389
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Chiang Mai University
Language: English
Description
Summary:This paper presents the implementation of shunt active power filter using source voltage and source current detection. The harmonic current and reactive power compensation of shunt active power filter controller is based on the digital signal processing (DSP) to control its operation. First, the signal quality of the designed prototype was tested with the simulation program. Then, the prototype for experiment has been setup for verifying the performance of system. It was found that reactive power could be compensated and harmonic current could be reduced, compared to the results of an active power filter with the load current detection. Since the source current detection used less controlling devices and its structure was simple, so it is more attractive. ©2008 IEEE.