Analysis of a heat pump with solid desiccant tube bank

In this paper, the analysis of silica gel formed in a staggered tube bank arrangement for the reduction of energy consumption in a heat pump dehumidifier is presented. The mathematical models for the desiccant and the heat pump have been developed. The simulated results agree quite well with those o...

全面介紹

Saved in:
書目詳細資料
Main Authors: Kiatsiriroat T., Tachajapong W.
格式: Article
語言:English
出版: 2014
在線閱讀:http://www.scopus.com/inward/record.url?eid=2-s2.0-0036572149&partnerID=40&md5=5a54aa6cb1c956e65cf6872511544ddc
http://cmuir.cmu.ac.th/handle/6653943832/1411
標簽: 添加標簽
沒有標簽, 成為第一個標記此記錄!
機構: Chiang Mai University
語言: English
實物特徵
總結:In this paper, the analysis of silica gel formed in a staggered tube bank arrangement for the reduction of energy consumption in a heat pump dehumidifier is presented. The mathematical models for the desiccant and the heat pump have been developed. The simulated results agree quite well with those of the experiments. The desiccant could reduce the heat pump load by about 7-20 per cent at the inlet air conditions of about 30-50°C and 70-90 per cent RH. Copyright © 2002 John Wiley & Sons, Ltd.