AC flashover performance of porcelain insulators in distribution systems

This paper presents an experiment on the different artificial pollution tests based on IEC 60507. The insulators, in the chamber for tests, used the standard medium system 22 kV. The insulators were tested with each type consisting of leakage current (LC) and flashover voltage (FOV) performance of t...

Full description

Saved in:
Bibliographic Details
Main Authors: Thippresert W., Jirapong P.
Format: Conference or Workshop Item
Language:English
Published: 2014
Online Access:http://www.scopus.com/inward/record.url?eid=2-s2.0-84861950005&partnerID=40&md5=30f83bba6fe508dadcc7919fc6d32029
http://cmuir.cmu.ac.th/handle/6653943832/1591
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Chiang Mai University
Language: English
Description
Summary:This paper presents an experiment on the different artificial pollution tests based on IEC 60507. The insulators, in the chamber for tests, used the standard medium system 22 kV. The insulators were tested with each type consisting of leakage current (LC) and flashover voltage (FOV) performance of the coating of the insulator surface, with and without semiconductor. The salt fog test results showed that FOV performance of the pin post insulator with surface without coating is less than 38 percent of dry test FOV level at equivalent salt deposit density (ESDD) = 0.5 mg/cm2. The LC of Line post insulator of a surface without a coating is less than three types of porcelain insulators, in the medium system, with 10 mA at ESDD = 0.3 mg/cm2, at a nominal voltage. This data will be useful as a guideline in cases to take insulators surface coating by the semiconductor of distribution system, to reduce the maintenance cost. Moreover, it will be useful to select or design the suitable insulators for use in polluted areas.