WLAV state estimation for power system containing multitype FACTS devices
This paper presents the state estimation of power system in which not only the bus voltages but also the states of the flexible AC transmission system (FACTS) are considered as the state variables. By using the rectangular form of state variables and equivalent measurement techniques, a linear measu...
Saved in:
Main Authors: | , , |
---|---|
Format: | Article |
Language: | English |
Published: |
2014
|
Online Access: | http://www.scopus.com/inward/record.url?eid=2-s2.0-84876468303&partnerID=40&md5=dc6aca8372641d1482a9ef8dd616dada http://cmuir.cmu.ac.th/handle/6653943832/1621 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Chiang Mai University |
Language: | English |
Summary: | This paper presents the state estimation of power system in which not only the bus voltages but also the states of the flexible AC transmission system (FACTS) are considered as the state variables. By using the rectangular form of state variables and equivalent measurement techniques, a linear measurement model with constraints of FACTS device is obtained. The predictor-corrector interior point method based on the weighted least absolute value criterion is developed for solving the optimization problem. Simulation results on the modified IEEE 14-bus and 118-bus test systems are provided. The numerical results indicate the effectiveness of the proposed approach. © 2013 Institute of Electrical Engineers of Japan. |
---|