Comparison of IEEE and IEC standards for calculations of insulation levels and electrical clearances for 230 kV air insulated substation

© 2016 IEEE. This paper compares the calculations of insulation levels and electrical clearances for 230 kV air insulated substation based on IEEE and IEC standards. The IEEE Std. 1427 can be applied for phase to ground and phase to phase insulations and electrical clearances calculations. Besides c...

Full description

Saved in:
Bibliographic Details
Main Author: T. Thanasaksiri
Format: Conference Proceeding
Published: 2018
Subjects:
Online Access:https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=84988892064&origin=inward
http://cmuir.cmu.ac.th/jspui/handle/6653943832/55506
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: Chiang Mai University
id th-cmuir.6653943832-55506
record_format dspace
spelling th-cmuir.6653943832-555062018-09-05T03:00:25Z Comparison of IEEE and IEC standards for calculations of insulation levels and electrical clearances for 230 kV air insulated substation T. Thanasaksiri Computer Science Engineering © 2016 IEEE. This paper compares the calculations of insulation levels and electrical clearances for 230 kV air insulated substation based on IEEE and IEC standards. The IEEE Std. 1427 can be applied for phase to ground and phase to phase insulations and electrical clearances calculations. Besides calculations, the simulation tool, EMTP as presents in IEEE Std. 1313.2 can be helpful for estimation the crest voltages at any location in substation. According to IEEE Std. 1427 which taking into account the basic switching impulse insulation levels (BSL), the iterative method is also required. At this voltage level, the procedure for calculations refer to IEC 60071-2 in range I can be applied. To compile with IEC 60071-2 for calculations the insulation levels and electrical clearances, the iteration process accounting for the standard rated switching impulse withstand voltage or BSL is not required but the test conversion factors have to be considered. The relation between insulation levels and electrical clearances applying IEEE and IEC standards are approximately linear. The insulation levels and electrical clearances when applied both standards are not significantly difference. 2018-09-05T02:57:21Z 2018-09-05T02:57:21Z 2016-09-06 Conference Proceeding 2-s2.0-84988892064 10.1109/ECTICon.2016.7561423 https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=84988892064&origin=inward http://cmuir.cmu.ac.th/jspui/handle/6653943832/55506
institution Chiang Mai University
building Chiang Mai University Library
country Thailand
collection CMU Intellectual Repository
topic Computer Science
Engineering
spellingShingle Computer Science
Engineering
T. Thanasaksiri
Comparison of IEEE and IEC standards for calculations of insulation levels and electrical clearances for 230 kV air insulated substation
description © 2016 IEEE. This paper compares the calculations of insulation levels and electrical clearances for 230 kV air insulated substation based on IEEE and IEC standards. The IEEE Std. 1427 can be applied for phase to ground and phase to phase insulations and electrical clearances calculations. Besides calculations, the simulation tool, EMTP as presents in IEEE Std. 1313.2 can be helpful for estimation the crest voltages at any location in substation. According to IEEE Std. 1427 which taking into account the basic switching impulse insulation levels (BSL), the iterative method is also required. At this voltage level, the procedure for calculations refer to IEC 60071-2 in range I can be applied. To compile with IEC 60071-2 for calculations the insulation levels and electrical clearances, the iteration process accounting for the standard rated switching impulse withstand voltage or BSL is not required but the test conversion factors have to be considered. The relation between insulation levels and electrical clearances applying IEEE and IEC standards are approximately linear. The insulation levels and electrical clearances when applied both standards are not significantly difference.
format Conference Proceeding
author T. Thanasaksiri
author_facet T. Thanasaksiri
author_sort T. Thanasaksiri
title Comparison of IEEE and IEC standards for calculations of insulation levels and electrical clearances for 230 kV air insulated substation
title_short Comparison of IEEE and IEC standards for calculations of insulation levels and electrical clearances for 230 kV air insulated substation
title_full Comparison of IEEE and IEC standards for calculations of insulation levels and electrical clearances for 230 kV air insulated substation
title_fullStr Comparison of IEEE and IEC standards for calculations of insulation levels and electrical clearances for 230 kV air insulated substation
title_full_unstemmed Comparison of IEEE and IEC standards for calculations of insulation levels and electrical clearances for 230 kV air insulated substation
title_sort comparison of ieee and iec standards for calculations of insulation levels and electrical clearances for 230 kv air insulated substation
publishDate 2018
url https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=84988892064&origin=inward
http://cmuir.cmu.ac.th/jspui/handle/6653943832/55506
_version_ 1681424518440026112