EXPERIMENT AND NUMERICAL STUDY ON TEMPERATURE DISTRIBUTION OF AN AIR- COOLED CONDENSER SIMULATOR
Sea wind entraining a couple of air-cooled chiller in a line damages the next chiller following the 1st chiller on the winds trajectory. Damage occured on the 2nd year of a total 15 year of normal chiller operation. Arrangement of chillers perpendicular to the winds direction seems to be a <br /...
Saved in:
Main Author: | |
---|---|
Format: | Final Project |
Language: | Indonesia |
Online Access: | https://digilib.itb.ac.id/gdl/view/15478 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Institut Teknologi Bandung |
Language: | Indonesia |
id |
id-itb.:15478 |
---|---|
spelling |
id-itb.:154782017-09-27T10:40:52ZEXPERIMENT AND NUMERICAL STUDY ON TEMPERATURE DISTRIBUTION OF AN AIR- COOLED CONDENSER SIMULATOR SURYOPRATOMO (NIM : 13105072); Dosen Pembimbing Dr.Ir.Prihadi Setyo Darmanto, EDO Indonesia Final Project INSTITUT TEKNOLOGI BANDUNG https://digilib.itb.ac.id/gdl/view/15478 Sea wind entraining a couple of air-cooled chiller in a line damages the next chiller following the 1st chiller on the winds trajectory. Damage occured on the 2nd year of a total 15 year of normal chiller operation. Arrangement of chillers perpendicular to the winds direction seems to be a <br /> <br /> <br /> solution to the problem. This solution can be proven by viewing the air temperature disribution along the condenser. <br /> <br /> <br /> Temperature distribution of the air can be viewed by an experiment involving a model of the condenser and utilizing a CFD numerical simulation. The model of condensor is geometrically scaled by 1:100. Experiment is conducted by variating the wind speed and direction and the spacing between condensers. Experiment and CFD both shows a similar <br /> <br /> <br /> result. <br /> <br /> <br /> Results shows a good chosen ratio of distance between fan centre’s and fan diameter for condensers in a line and perpendicular with sea wind, respectively, is achieved at a minimum of 9 dan 3,8. <br /> <br /> <br /> At a city impeded by sea wind, where a number of air-cooled condensers are needed, the arrangement of condensers should be perpendicular with the wind trajectory. In addition, a ratio of distance between centres of fan and fan diameter should be held a minimum of 3,8. text |
institution |
Institut Teknologi Bandung |
building |
Institut Teknologi Bandung Library |
continent |
Asia |
country |
Indonesia Indonesia |
content_provider |
Institut Teknologi Bandung |
collection |
Digital ITB |
language |
Indonesia |
description |
Sea wind entraining a couple of air-cooled chiller in a line damages the next chiller following the 1st chiller on the winds trajectory. Damage occured on the 2nd year of a total 15 year of normal chiller operation. Arrangement of chillers perpendicular to the winds direction seems to be a <br />
<br />
<br />
solution to the problem. This solution can be proven by viewing the air temperature disribution along the condenser. <br />
<br />
<br />
Temperature distribution of the air can be viewed by an experiment involving a model of the condenser and utilizing a CFD numerical simulation. The model of condensor is geometrically scaled by 1:100. Experiment is conducted by variating the wind speed and direction and the spacing between condensers. Experiment and CFD both shows a similar <br />
<br />
<br />
result. <br />
<br />
<br />
Results shows a good chosen ratio of distance between fan centre’s and fan diameter for condensers in a line and perpendicular with sea wind, respectively, is achieved at a minimum of 9 dan 3,8. <br />
<br />
<br />
At a city impeded by sea wind, where a number of air-cooled condensers are needed, the arrangement of condensers should be perpendicular with the wind trajectory. In addition, a ratio of distance between centres of fan and fan diameter should be held a minimum of 3,8. |
format |
Final Project |
author |
SURYOPRATOMO (NIM : 13105072); Dosen Pembimbing Dr.Ir.Prihadi Setyo Darmanto, EDO |
spellingShingle |
SURYOPRATOMO (NIM : 13105072); Dosen Pembimbing Dr.Ir.Prihadi Setyo Darmanto, EDO EXPERIMENT AND NUMERICAL STUDY ON TEMPERATURE DISTRIBUTION OF AN AIR- COOLED CONDENSER SIMULATOR |
author_facet |
SURYOPRATOMO (NIM : 13105072); Dosen Pembimbing Dr.Ir.Prihadi Setyo Darmanto, EDO |
author_sort |
SURYOPRATOMO (NIM : 13105072); Dosen Pembimbing Dr.Ir.Prihadi Setyo Darmanto, EDO |
title |
EXPERIMENT AND NUMERICAL STUDY ON TEMPERATURE DISTRIBUTION OF AN AIR- COOLED CONDENSER SIMULATOR |
title_short |
EXPERIMENT AND NUMERICAL STUDY ON TEMPERATURE DISTRIBUTION OF AN AIR- COOLED CONDENSER SIMULATOR |
title_full |
EXPERIMENT AND NUMERICAL STUDY ON TEMPERATURE DISTRIBUTION OF AN AIR- COOLED CONDENSER SIMULATOR |
title_fullStr |
EXPERIMENT AND NUMERICAL STUDY ON TEMPERATURE DISTRIBUTION OF AN AIR- COOLED CONDENSER SIMULATOR |
title_full_unstemmed |
EXPERIMENT AND NUMERICAL STUDY ON TEMPERATURE DISTRIBUTION OF AN AIR- COOLED CONDENSER SIMULATOR |
title_sort |
experiment and numerical study on temperature distribution of an air- cooled condenser simulator |
url |
https://digilib.itb.ac.id/gdl/view/15478 |
_version_ |
1820737476676812800 |