PERFORMANCE EVALUATION AND ENERGY EFFICIENCY IMPROVEMENT OF HOT WATER SYSTEM AT HOTEL
Hot water systemin a four stars hotel building requires big energy consumption. <br /> <br /> <br /> Energy efficiency evaluation of hot water system will gives information about the <br /> <br /> <br /> system performance, so energy efficiency improvement can...
Saved in:
Main Author: | |
---|---|
Format: | Final Project |
Language: | Indonesia |
Online Access: | https://digilib.itb.ac.id/gdl/view/21285 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Institut Teknologi Bandung |
Language: | Indonesia |
Summary: | Hot water systemin a four stars hotel building requires big energy consumption. <br />
<br />
<br />
Energy efficiency evaluation of hot water system will gives information about the <br />
<br />
<br />
system performance, so energy efficiency improvement can applied more spesific. <br />
<br />
<br />
The energy efficiency evaluation in a four stars hotel building including boiler <br />
<br />
<br />
efficiency calculation, pumps efficiency calculation, heat transfer per meter at hot <br />
<br />
<br />
water tank, and heat transfer per meter at hot water piping system. <br />
<br />
<br />
Based on those calculation,boiler 1 efficiency variated from 37,7% to 40,8%. <br />
<br />
<br />
Meanwhile,boiler 2 efficiency variated from 37,3% to 42,6%. Avarage efficiency <br />
<br />
<br />
of circulation pump is 50,04% and average efficiency of distribution pump is <br />
<br />
<br />
61,91%. Heat transfer per meter value at hot water tank 1 is 30,07W/m and heat <br />
<br />
<br />
transfer per meter value at hot water tank 2 is 29,9W/m. Meanwhile, heat transfer <br />
<br />
<br />
value per meterat hot water piping system variated from 3,8W/m to 72W/m.If hot <br />
<br />
<br />
water pipe insulated by 25mm glasswool, heat transfer will decreased, so water <br />
<br />
<br />
temperatur will reserved. |
---|