PERFORMANCE EVALUATION AND ENERGY EFFICIENCY IMPROVEMENT OF HOT WATER SYSTEM AT HOTEL
Hot water systemin a four stars hotel building requires big energy consumption. <br /> <br /> <br /> Energy efficiency evaluation of hot water system will gives information about the <br /> <br /> <br /> system performance, so energy efficiency improvement can...
Saved in:
Main Author: | |
---|---|
Format: | Final Project |
Language: | Indonesia |
Online Access: | https://digilib.itb.ac.id/gdl/view/21285 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Institut Teknologi Bandung |
Language: | Indonesia |
id |
id-itb.:21285 |
---|---|
spelling |
id-itb.:212852017-09-27T11:05:22ZPERFORMANCE EVALUATION AND ENERGY EFFICIENCY IMPROVEMENT OF HOT WATER SYSTEM AT HOTEL Wijaya (NIM : 13311058) Kiki Intan Mayangsari (NIM : 13311014), Asra Indonesia Final Project INSTITUT TEKNOLOGI BANDUNG https://digilib.itb.ac.id/gdl/view/21285 Hot water systemin a four stars hotel building requires big energy consumption. <br /> <br /> <br /> Energy efficiency evaluation of hot water system will gives information about the <br /> <br /> <br /> system performance, so energy efficiency improvement can applied more spesific. <br /> <br /> <br /> The energy efficiency evaluation in a four stars hotel building including boiler <br /> <br /> <br /> efficiency calculation, pumps efficiency calculation, heat transfer per meter at hot <br /> <br /> <br /> water tank, and heat transfer per meter at hot water piping system. <br /> <br /> <br /> Based on those calculation,boiler 1 efficiency variated from 37,7% to 40,8%. <br /> <br /> <br /> Meanwhile,boiler 2 efficiency variated from 37,3% to 42,6%. Avarage efficiency <br /> <br /> <br /> of circulation pump is 50,04% and average efficiency of distribution pump is <br /> <br /> <br /> 61,91%. Heat transfer per meter value at hot water tank 1 is 30,07W/m and heat <br /> <br /> <br /> transfer per meter value at hot water tank 2 is 29,9W/m. Meanwhile, heat transfer <br /> <br /> <br /> value per meterat hot water piping system variated from 3,8W/m to 72W/m.If hot <br /> <br /> <br /> water pipe insulated by 25mm glasswool, heat transfer will decreased, so water <br /> <br /> <br /> temperatur will reserved. text |
institution |
Institut Teknologi Bandung |
building |
Institut Teknologi Bandung Library |
continent |
Asia |
country |
Indonesia Indonesia |
content_provider |
Institut Teknologi Bandung |
collection |
Digital ITB |
language |
Indonesia |
description |
Hot water systemin a four stars hotel building requires big energy consumption. <br />
<br />
<br />
Energy efficiency evaluation of hot water system will gives information about the <br />
<br />
<br />
system performance, so energy efficiency improvement can applied more spesific. <br />
<br />
<br />
The energy efficiency evaluation in a four stars hotel building including boiler <br />
<br />
<br />
efficiency calculation, pumps efficiency calculation, heat transfer per meter at hot <br />
<br />
<br />
water tank, and heat transfer per meter at hot water piping system. <br />
<br />
<br />
Based on those calculation,boiler 1 efficiency variated from 37,7% to 40,8%. <br />
<br />
<br />
Meanwhile,boiler 2 efficiency variated from 37,3% to 42,6%. Avarage efficiency <br />
<br />
<br />
of circulation pump is 50,04% and average efficiency of distribution pump is <br />
<br />
<br />
61,91%. Heat transfer per meter value at hot water tank 1 is 30,07W/m and heat <br />
<br />
<br />
transfer per meter value at hot water tank 2 is 29,9W/m. Meanwhile, heat transfer <br />
<br />
<br />
value per meterat hot water piping system variated from 3,8W/m to 72W/m.If hot <br />
<br />
<br />
water pipe insulated by 25mm glasswool, heat transfer will decreased, so water <br />
<br />
<br />
temperatur will reserved. |
format |
Final Project |
author |
Wijaya (NIM : 13311058) Kiki Intan Mayangsari (NIM : 13311014), Asra |
spellingShingle |
Wijaya (NIM : 13311058) Kiki Intan Mayangsari (NIM : 13311014), Asra PERFORMANCE EVALUATION AND ENERGY EFFICIENCY IMPROVEMENT OF HOT WATER SYSTEM AT HOTEL |
author_facet |
Wijaya (NIM : 13311058) Kiki Intan Mayangsari (NIM : 13311014), Asra |
author_sort |
Wijaya (NIM : 13311058) Kiki Intan Mayangsari (NIM : 13311014), Asra |
title |
PERFORMANCE EVALUATION AND ENERGY EFFICIENCY IMPROVEMENT OF HOT WATER SYSTEM AT HOTEL |
title_short |
PERFORMANCE EVALUATION AND ENERGY EFFICIENCY IMPROVEMENT OF HOT WATER SYSTEM AT HOTEL |
title_full |
PERFORMANCE EVALUATION AND ENERGY EFFICIENCY IMPROVEMENT OF HOT WATER SYSTEM AT HOTEL |
title_fullStr |
PERFORMANCE EVALUATION AND ENERGY EFFICIENCY IMPROVEMENT OF HOT WATER SYSTEM AT HOTEL |
title_full_unstemmed |
PERFORMANCE EVALUATION AND ENERGY EFFICIENCY IMPROVEMENT OF HOT WATER SYSTEM AT HOTEL |
title_sort |
performance evaluation and energy efficiency improvement of hot water system at hotel |
url |
https://digilib.itb.ac.id/gdl/view/21285 |
_version_ |
1821120415397838848 |