EFFECTIVENESS OF DOUBLE SKIN FACADE AS RETROFIT TO REDUCE ENERGY OPERATIONAL CONSUMPTION OF RENT OFFICE BUILDING
Increasing energy needs amid limited sources of energy, especially to create a comfortable environment in the building to be reasons for energy saving measures. Building as a large environmental burden became one of the sectors that have potential to reduce energy consumption. Energy saving measu...
Saved in:
Main Author: | |
---|---|
Format: | Theses |
Language: | Indonesia |
Subjects: | |
Online Access: | https://digilib.itb.ac.id/gdl/view/33293 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Institution: | Institut Teknologi Bandung |
Language: | Indonesia |
id |
id-itb.:33293 |
---|---|
spelling |
id-itb.:332932019-01-18T15:06:05ZEFFECTIVENESS OF DOUBLE SKIN FACADE AS RETROFIT TO REDUCE ENERGY OPERATIONAL CONSUMPTION OF RENT OFFICE BUILDING Aslim, Nurfadhilah Desain dan dekorasi bangunan dan aksesori Indonesia Theses Retrofit, DSF, Cooling load, Operational Energy Consumption, OTTV. INSTITUT TEKNOLOGI BANDUNG https://digilib.itb.ac.id/gdl/view/33293 Increasing energy needs amid limited sources of energy, especially to create a comfortable environment in the building to be reasons for energy saving measures. Building as a large environmental burden became one of the sectors that have potential to reduce energy consumption. Energy saving measures through the most efficient retrofit strategy on building starts of the building envelope. Through DSF as avoid heating technology thus creates a comfortable thermal environment that can reduce the energy consumption of buildings. This study tries to prove that the angle on the configuration of the DSF have effectiveness in reducing indoor air temperatures and reduce operational energy use of the building by using digital simulation with OpenStudio. The results showed the DSF is able to lower the OTTV value of 21.53W/m2 or 29% from the previous value, lower the air temperature in the building until 3.43°C and reduce 11.6% - 57% of building operational energy consumption. DSF as a retrofit buildings will provide benefits for the long term. With the result that DSF in office buildings or other high rise buildings can be a solution of the current energy crisis through energy saving measures. text |
institution |
Institut Teknologi Bandung |
building |
Institut Teknologi Bandung Library |
continent |
Asia |
country |
Indonesia Indonesia |
content_provider |
Institut Teknologi Bandung |
collection |
Digital ITB |
language |
Indonesia |
topic |
Desain dan dekorasi bangunan dan aksesori |
spellingShingle |
Desain dan dekorasi bangunan dan aksesori Aslim, Nurfadhilah EFFECTIVENESS OF DOUBLE SKIN FACADE AS RETROFIT TO REDUCE ENERGY OPERATIONAL CONSUMPTION OF RENT OFFICE BUILDING |
description |
Increasing energy needs amid limited sources of energy, especially to create a
comfortable environment in the building to be reasons for energy saving
measures. Building as a large environmental burden became one of the sectors
that have potential to reduce energy consumption. Energy saving measures
through the most efficient retrofit strategy on building starts of the building
envelope. Through DSF as avoid heating technology thus creates a comfortable
thermal environment that can reduce the energy consumption of buildings.
This study tries to prove that the angle on the configuration of the DSF have
effectiveness in reducing indoor air temperatures and reduce operational energy
use of the building by using digital simulation with OpenStudio. The results
showed the DSF is able to lower the OTTV value of 21.53W/m2 or 29% from the
previous value, lower the air temperature in the building until 3.43°C and reduce
11.6% - 57% of building operational energy consumption. DSF as a retrofit
buildings will provide benefits for the long term. With the result that DSF in office
buildings or other high rise buildings can be a solution of the current energy
crisis through energy saving measures. |
format |
Theses |
author |
Aslim, Nurfadhilah |
author_facet |
Aslim, Nurfadhilah |
author_sort |
Aslim, Nurfadhilah |
title |
EFFECTIVENESS OF DOUBLE SKIN FACADE AS RETROFIT TO REDUCE ENERGY OPERATIONAL CONSUMPTION OF RENT OFFICE BUILDING |
title_short |
EFFECTIVENESS OF DOUBLE SKIN FACADE AS RETROFIT TO REDUCE ENERGY OPERATIONAL CONSUMPTION OF RENT OFFICE BUILDING |
title_full |
EFFECTIVENESS OF DOUBLE SKIN FACADE AS RETROFIT TO REDUCE ENERGY OPERATIONAL CONSUMPTION OF RENT OFFICE BUILDING |
title_fullStr |
EFFECTIVENESS OF DOUBLE SKIN FACADE AS RETROFIT TO REDUCE ENERGY OPERATIONAL CONSUMPTION OF RENT OFFICE BUILDING |
title_full_unstemmed |
EFFECTIVENESS OF DOUBLE SKIN FACADE AS RETROFIT TO REDUCE ENERGY OPERATIONAL CONSUMPTION OF RENT OFFICE BUILDING |
title_sort |
effectiveness of double skin facade as retrofit to reduce energy operational consumption of rent office building |
url |
https://digilib.itb.ac.id/gdl/view/33293 |
_version_ |
1821996474722942976 |