Hydraulic calculation of district cooling distribution network with ICE thermal energy storage system

Hydraulic calculation of a simple distribution network of district cooling plant (DCP) with ice thermal energy storage (TES) system is presented wherein the system pressure drop and flow rate requirements in each energy transfer station (ETS) are determined considering a system temperature differenc...

Full description

Saved in:
Bibliographic Details
Main Authors: Augusto, Gerardo L., Maglaya, Archie B.
Format: text
Published: Animo Repository 2011
Subjects:
Online Access:https://animorepository.dlsu.edu.ph/faculty_research/12010
Tags: Add Tag
No Tags, Be the first to tag this record!
Institution: De La Salle University
Description
Summary:Hydraulic calculation of a simple distribution network of district cooling plant (DCP) with ice thermal energy storage (TES) system is presented wherein the system pressure drop and flow rate requirements in each energy transfer station (ETS) are determined considering a system temperature difference set-point of 11oC.Variable primary flow pumping in chilled water system was used as a benchmark to calculate the theoretical system pressure drop of distribution network. The system of nonlinear equation s consisted of pump performance curve and system characteristic curves of distribution network with twelve (12) energy transfer stations.Multivariable Newton_Raphson and LU Decomposition methods were used in solving the nonlinear equations. Method of least squares and Cholesky decomposition were adopted to derive new sets of pump characteristic curves taken from Similarity Laws considering that pumps are modulated at its best efficiency point during full load condition.