Lightning performance of covered conductors overhead distribution lines

This paper analyzes the lightning performance of 22 kV, ChiangMai substation 4 to Doi-Suthep, overhead distribution line with covered conductors. The performance of line which related to the insulator flashover has been modeled and analyzed using EMTP. The backflashover rate (BFOR), shielding failur...

全面介紹

Saved in:
書目詳細資料
主要作者: Thanasaksiri T.
格式: Conference Proceeding
出版: 2017
在線閱讀:https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=77954925654&origin=inward
http://cmuir.cmu.ac.th/jspui/handle/6653943832/43262
標簽: 添加標簽
沒有標簽, 成為第一個標記此記錄!
機構: Chiang Mai University
實物特徵
總結:This paper analyzes the lightning performance of 22 kV, ChiangMai substation 4 to Doi-Suthep, overhead distribution line with covered conductors. The performance of line which related to the insulator flashover has been modeled and analyzed using EMTP. The backflashover rate (BFOR), shielding failure flashover rate (SFFOR) and induced voltage flashover rate (IVFOR) of line have been determined. The number of lightning flashovers from simulation, by applying ground flash density Ng=6.5x10-5Td 2.277, are close with the data from the line outages recorder.