Analysis of power system event using synchronized PMUs in Thailand power network
This paper applies the synchronized phasor measurement units (PMUs) based wide-area monitoring system to analyze the power system event under the occurrence of large disturbance. The salient feature of the monitoring system is the convenient installation of PMU at 220 V home outlet. The power system...
Saved in:
Main Authors: | , , , , , , , , , , , , |
---|---|
格式: | Conference Proceeding |
出版: |
2018
|
主題: | |
在線閱讀: | https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=54949112868&origin=inward http://cmuir.cmu.ac.th/jspui/handle/6653943832/61048 |
標簽: |
添加標簽
沒有標簽, 成為第一個標記此記錄!
|
機構: | Chiang Mai University |
總結: | This paper applies the synchronized phasor measurement units (PMUs) based wide-area monitoring system to analyze the power system event under the occurrence of large disturbance. The salient feature of the monitoring system is the convenient installation of PMU at 220 V home outlet. The power system event given here is the tripping of High-Voltage Direct Current (HVDC) link between Thailand and Malaysia due to the fault in a thyristor room at Khlong Ngae converter station of Thailand side on July 22, 2005. The discrete wavelet decomposition and short-time Fourier Transform have been applied to analyze the characteristic of the inter-area oscillation between central and southern areas in both time and frequency domains. Analyzed results based on PMUs data are consistent with the actual tie-line power flow between both areas. |
---|